Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
◦ Web server port configuration (to avoid loss of Ethernet connectivity)
◦ Line power channels (unique to line power modules)
◦
Power module (power modules are unique to a system)
◦
Users (to maintain password security)
◦
Server passwords (for example, email server password; to maintain password
security)
To export settings:
1. Fromthemaindashboardgoto,Controller > Files & Upgrades > Configuration & Software
Backup.
2.
Selectthetypeofexportrequired:
◦ Export Controller Clone:Afileisgeneratedanduploadedtoyourbrowser.
◦
Export System or ADIO:AwizarddisplaysinwhichyoucanselectaSystemoranADIO
module.SelectanitemtoexportandthenselectNext.UsetheDownload File optionto
saveyourexportfile.
◦
Export Partial:Awizarddisplaysinwhichyoucanselectaconfigurationsource,select
Next.IntheSelect Configuration to Export window,selecteachconfigurationitemfor
export,selectNext.InSelect Another Configuration window,selectYes andselectNext
toselectanotherconfigurationsource.SelectNo andselectNext whenallconfiguration
itemareselected.Oncetheconfigurationfileisprepared,usetheDownload File optionto
saveyourexportfile.
3. Tohelpdistinguishamongconfigurationfilesrenameyourexportfilewithauniqueidentifier.This
canimportantwhenmakingaback-upfilesforarchivingorifacontrollerreplacementisrequired.
20.5.5. Import a configuration file
Whenimportingaconfigurationfile,thecontrollerwillanalyzethefiletodeterminethetypeofimportto
perform.Therearethreetypesofimportcorrespondingtothethreetypesofexport.
Clone
CloneisperformedwhenafilethathasbeenexportedusingExport Clone Controller isuploaded.The
configurationofthecontrollerismatchedtothatcontainedinthefile.Inadditionallexistingsystems,
customdata,timers,counters,datalogsareremoved.Cloneisalsoperformedifaconfigurationfilefroma
versionprevioustoversion4.00isuploaded.
Copy system or ADIO module
0350058-J0 Rev AL Page 201