Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
Web server port configuration (to avoid loss of Ethernet connectivity)
Line power channels (unique to line power modules)
Power module (power modules are unique to a system)
Users (to maintain password security)
Server passwords (for example, email server password; to maintain password
security)
To export settings:
1. Fromthemaindashboardgoto,Controller > Files & Upgrades > Configuration & Software
Backup.
2.
Selectthetypeofexportrequired:
Export Controller Clone:Afileisgeneratedanduploadedtoyourbrowser.
Export System or ADIO:AwizarddisplaysinwhichyoucanselectaSystemoranADIO
module.SelectanitemtoexportandthenselectNext.UsetheDownload File optionto
saveyourexportfile.
Export Partial:Awizarddisplaysinwhichyoucanselectaconfigurationsource,select
Next.IntheSelect Configuration to Export window,selecteachconfigurationitemfor
export,selectNext.InSelect Another Configuration window,selectYes andselectNext
toselectanotherconfigurationsource.SelectNo andselectNext whenallconfiguration
itemareselected.Oncetheconfigurationfileisprepared,usetheDownload File optionto
saveyourexportfile.
3. Tohelpdistinguishamongconfigurationfilesrenameyourexportfilewithauniqueidentifier.This
canimportantwhenmakingaback-upfilesforarchivingorifacontrollerreplacementisrequired.
20.5.5. Import a configuration file
Whenimportingaconfigurationfile,thecontrollerwillanalyzethefiletodeterminethetypeofimportto
perform.Therearethreetypesofimportcorrespondingtothethreetypesofexport.
Clone
CloneisperformedwhenafilethathasbeenexportedusingExport Clone Controller isuploaded.The
configurationofthecontrollerismatchedtothatcontainedinthefile.Inadditionallexistingsystems,
customdata,timers,counters,datalogsareremoved.Cloneisalsoperformedifaconfigurationfilefroma
versionprevioustoversion4.00isuploaded.
Copy system or ADIO module
0350058-J0 Rev AL Page 201

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish