Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
TheModules Alerts logtabletrackswhatishappeningonindividualmoduleswithoutinterferingwith
Alarms ortheEvent log.
20.4.2. Battery log
TheBattery logrecordsthedurationandchangeincapacity(Ah)foreverychargeanddischargeofa
battery.IfyouhaveBattery Runtime & Heath enabled,thelogwillalsorecordthechangeinState of
Charge (SOC) andState of Health (SOH).
Becauseofthelargequantityofinformationthatcanbecollectedforbatterychargesanddischarges,a
completedatasetcanonlytoobtainedbyexportingthelog.Thefollowingthreefiguresprovideexamples
ofthedata.
WhenviewedontheLCD,thelogshowstime,activitytype,durationandamphoursdelivered.
Whenviewedonthewebinterface,thelogincludesthebatteryID,batterycapacity,stateofcharge,state
ofhealth,andtheactivityresults.
WhenexportedtoaCSVfile,thelogincludesthePeukertexponent,startingandendingvoltagesplusthe
minimum,maximumandaveragebatterycurrentsandtemperatures.
Thebatterylogwillholdupto300entriesinaFIFO.WhenviewingentriesontheLCD,upto25canbe
viewed.All300entriesmaybeviewedonthewebinterfaceorexportedtoaCSVfile.
Figure 20-2 Batterylogonthewebinterface
Figure 20-3 BatteryloginExcel
20.4.3. Power outage log
ThePower Outage logrecordstimeanddurationofeverypoweroutagetothesystem.Ifyouhave
Battery Runtime & Heath enabled,youcanrefertotheBatterylogtodeterminethechangeinState of
Charge (SOC) andState of Health (SOH).
0350058-J0 Rev AL Page 193