Cordex®CXCHPControllerSoftwareManual|12-ACsourcesystems
◦ ASimple AC Source canbeusedtomodelanACsourcewithvoltagereadingsforeach
phase.ThissourceincludesAC Fail andUrgent AC Fail alarms.
◦ AGenerator isaspecializedtypeofACsourcewhichcanautomaticallycontrolthestarting
andstoppingofageneratorwiththeuseofarelay,basedonconditionsspecified.
◦ ALegacy Generator canalsoautomaticallycontrolthestartingandstoppingofagenerator,
buthasbeensucceededbytheGeneratoroption.
5. SelectthePhase foryourAC Source.
6. OntheAlarms page,selectwhethertheACInputFailalarmshouldbeenabledforthissource.
SelectYes orNo.
7. OntheVoltage Readings page,selectthesystemfromwhichtheACsourcewillobtainits
readings.
8. IfaDCsystemwaschosenfortheVoltage Readings sourceinstep7,therewillbeanoptionto
launchtheMap Rectifiers to AC Source wizardontheResults page.
Notice: If the Voltage Reading Source System has been set to a DC system, the phase voltage
sources will be automatically set to the mapped rectifiers. If the Voltage Reading Source
System has been set to an Inverter system, these phase voltage sources will be set to read from
the Inverter system. If the Voltage Reading Source System is left unknown, these phase voltage
sources should be set to read from transducers or any other voltage sources as desired.
Notice: If the Voltage Reading Source System has been set to a DC system, and the AC Fail
alarms are enabled, the AC Input Fail alarm will be calculated in the same manner as the DC
system’s AC Fail alarm. If 90 percent of the rectifiers mapped to this AC source have failed, then
the AC Input is assumed to be failed. Otherwise, if the Voltage Reading Source System is set to
an Inverter system, or left unset, the AC Input Fail alarm will be activated if any one of the phase
voltages falls below 10 V.
12.2.1. Map rectifiers to an AC source
AnAC Source cangetitsdatafromeitheraDCsystem,aninvertersystem,orfromtransducers.
To map rectifiers from a DC system to an AC source:
1. LaunchtheMap Rectifiers to AC Source wizard.Thiscaneitherberundirectlyfromthe
resultspageoftheAdd AC Source wizard,orlaunchedfromSystems > AC Source System >
Inventory > AC Source page.
2. ChooserectifierstomapfromtheSelected column.Ifrectifiershavepreviouslybeenmappedto
thissource,theywillshowasselected.SelectNext.
3. TheReview stepwillshowthechangesrequested.SelectingCancel atthistimewilldiscardyour
changes.SelectNext toacceptyourchanges.
ThechosenrectifierswillbemappedtothisACSource.
Page 138 0350058-J0 Rev AL