Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
20.2.6. Alarm summary relays
Therearethreealarmsummaryrelaysthatcanbeconfiguredonthecontroller.Theserelaysare
connectedtoexternalmonitoringequipmentwhichprovidesanotificationwhenthecontrollerentersan
alarmstate.
Controllercriticalrelay
Controllermajorrelay
Controllerminorrelay
Toviewthem,gotoAlarms > Settings > Alarm Summary Relay.
TherelaymappedtotheController Critical Relay isactivewheneveroneormorecriticalalarmsare
active.Controller Major Relay,Controller Minor Relay,andController Warning Relay workinthe
sameway.
20.2.7. Create user alarms
Thecontrollerhasasetofdefaultstandardalarmsthatareassociatedwithasystemoraninventory
itemsuchasaloadoradisconnect.Thesestandardalarmsmaybeenoughtosupportmanysystem
configurations.Itisalsocommontoneedadditionalalarms,basedonthestatusofthedigitalinputsoron
thethresholdofananalogvaluereadfromtheinputofanADIOmodule.
Youcancreateanynumberofdigitalorthresholdalarms.Thesealarmshavethesamebehavioras
standardalarmssuchasalarmcut-off,SNMPtraps,andrelaymapping.Theseuser-definedalarmscan
becreatedandremovedviatheController > Programmability > User Alarms menu.
To create a user alarm:
1. GotoController > Programmability > User Alarms.
2.
Selectthetypeofuseralarmtocreate.Anewrowfortheuseralarmwilldisplayinthetable.
IfyouwanttocreateadigitalalarmselecttheAdd Digital User Alarm button.
IfyouwanttocreateahighorlowthresholdalarmselecttheAdd Threshold User Alarm
button.
3. SelecttheGO TO buttoninthealarmlineitem.Twotablesdisplay.Onetableshowsthefieldsto
configurethatarespecifictotheselecteduseralarm.Theothertableshowsthestandardalarm
configuration.
4. Givethealarmadescriptivename.Thisisimportantsincethesametypeofuseralarmshavethe
samedefaultname.Thealarmdescriptionisoptional.
5.
Selectthealarminputsource.Therearedifferentoptionsdependingonthetypeofuseralarmyou
arecreating.
0350058-J0 Rev AL Page 183

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish