Cordex®CXCHPControllerSoftwareManual|19-Maintainingthesystem
1. GotoSystems > Line Power System > Layout toidentifytheshelfandslotofthefailedmodule.
Amodulecausinganalarmwillbehighlightedwitharedborder.Ifthereismorethanonemodule
inalertitmaybenecessarytoselectthechannel,thenselectthemoduledetailslinktodetermine
thecauseofthefailure.
2. Unplugthefailedmoduleandreplaceitwithanewmodule.
3. SelecttheForget All in Comms Lost buttoninordertocleartheLP Module Comms Lost alarm.
Thenewmoduleisacquiredanditschannelsareautomaticallyassignedtothesameloadthattheold
modulewasassignedto.
19.4. Battery maintenance
Thissectioncoversthefollowing:batteryalarms,chargingbatteries,andmaintainingbatteries.
19.4.1. Battery alarms
ToviewtheBattery Alarms menugotoSystems > DC System > Inventory > Battery.
Whenthebatterychargecurrentexceedsthethreshold,theBattery Charge Current High alarmis
active.Thealarmmayoccurduringbatterychargingiftherearelargeloadfluctuations.Thealarmcan
alsobecausedbyanincorrectalarmthresholdorbatterychargecurrentlimitsetting.Thealarmwillclear
whenthebatterychargecurrentislessthanorequaltothethresholdminusthehysteresis.
Whenthehighestbatterytemperaturevaluerisesabovethethreshold,theBattery Temperature High
alarmisactive.Thealarmwillclearwhenthehighestbatterytemperaturevalueislessthanorequalto
thethresholdminushysteresis.
Whenthelowestbatterytemperaturevaluehasfallenbelowthethreshold,theBattery Temperature Low
alarmisactive.Thealarmwillclearwhenthelowestbatterytemperatureisgreaterthanorequaltothe
thresholdplushysteresis.
Inabatterysystem,theBattery Breaker/Fuse Open alarmwilltriggerwheneverybatterystringwithin
thebatterysystemhasabreakerorfusethathasopened.
EachbatterystringwithinabatterysystemhasitsownBattery Breaker/Fuse Open alarmwhichcango
activewhenthebatterybreakerorfuseisopen.Thealarmcanoccurwhenthedigitalinputthatdetects
thestateofthebreakerorfuseisactive.Toverifyconfiguration,theBreaker/Fuse Source oneach
batterystringcanbeverified.Thissourceistypicallyassignedtoadigitalinputsourcethatdetectsthe
stateofabreakerorfuse.Thealarmmayalsobecausedbyincorrectorfaultywiringorincorrectdigital
inputsettings.Thealarmwillclearwhenthedigitalinputisnotactive.
Whenthebatteryvoltageminusthemidpointvoltagemeasurementisgreaterthanthethreshold,the
Midpoint Unbalanced alarmisactive.Thealarmcanbecausedbyanimbalanceinbatterycellsor
blocksandmayindicateanequalizechargeisnecessary.Thealarmmayalsobecausedbydamaged
orend-of-lifecells.Thealarmwillclearwhenthedifferencebetweenhalfthebatteryvoltageandthe
midpointvoltageislessthanorequaltothethresholdminusthehysteresis.
Page 172 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish