Cordex®CXCHPControllerSoftwareManual|23-Troubleshooting
4. Placethenewrectifierintheshelf.
5. RectifiersarePlugandPlay,butyoumaystillneedtomapthenewrectifiertoanACphase.
6. IftherectifiershowsintheModules Available for Assignment table,insteadofintheStatus
table,selectAssign toassignthenewrectifier.
7. Confirmtheassignment.
23.2.6. Using extended ranges
Ifyour12Vdc,24Vdc,or48Vdcsystemhasabatteryandrectifiermodulesthatcanoperateoutsideof
thenormalranges,youcanenableextendedrangestoallowyourDCsystemtorunoutsidethenormal
ranges.
23.2.6.1. Extended ranges for battery testing
Normally,12Vdc,24Vdc,and48Vdcsystemshaveafairlynarrowrangeofvoltagesallowedforbattery
testing.Thesevoltagesarebasedonwhatisconsiderednormalforthebatteriesandwhatispossiblefor
therectifiers.Therangesaresetthiswaytoavoiderrorswhenconfiguringanewsystem.The125Vdc
and220Vdcsystemshaveawiderrangeofbatterytestvoltagesbecausethereareawidervarietyof
batteryconfigurationsusedwiththosesystems.
1. GotoSystems > DC System > Configure System.Intheconfigurationtable,changethe
Extended Ranges (Advanced) settingfromNormal toExtended.
2. GotoSystems > DC System > Inventory > Rectifiers > Configuration.Intheconfiguration
table,settheMinimum Test Voltage tothelowestvalueallowedbyyourrectifier.
3.
GotoSystems > DC System > System Functions > Battery Test.Intheconfigurationtable,set
theBattery Test Termination Voltage tothevoltageyouwantthebatterytesttorunto.
WestronglyrecommendthattheBattery Test Termination Voltage onthebatterytestpagebeat
least0.5voltshigherthantheMinimum Test Voltage ontherectifierconfigurationpage.
23.2.6.2. Extended ranges for battery equalization
Normally,batteryequalizationisaprocessdesignedtode-sulphateabattery’splatesbyholdinga
controlledoverchargeovertheperiodofafewhours.TheExtended Ranges optionwillallowmuch
longerdurationsthanisgenerallyusedforthebatteryequalizationprocess.Thisoptionhelpstosupport
systemswithunusualconfigurations.
CAUTION: Equalization for extended periods can cause excessive gassing and plate damage.
1. GotoSystems > DC System > Configure System.IntheConfiguration table,changethe
Extended Ranges (Advanced) settingfromNormal toExtended.
2. GotoSystems > DC System > System Functions > Equalize & Boost.IntheEqualize table,
changetheEqualize Duration settingtothedesiredtimelength.
0350058-J0 Rev AL Page 259

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish