Cordex®CXCHPControllerSoftwareManual|8-Linepowersystems
1. GotoSystems > Add or Remove Systems andselecttheCreate System button.
2. SelectCreate Line Power System fromthedropdownlist.TheCreate Line Power System
wizardwilllaunch.
3. Namethesystemifrequired.
4. FromtheSelect System Type dropdownlist,selectthevaluethatcorrespondstoyourline
powermoduletype.Iftherearelinepowermodulesalreadyconnectedtothecontroller,theyare
preselectedwiththecorrectoption.
5. Followtherestofthewizardinstructions.
8.2.1. Create a system from a configuration file
Asystemcanbecreatedbyimportingfromaconfigurationfile.SeetheImporting a system sectionfor
moreinformation.
8.3. Configure the line power modules
Therearetwosettingsthatareappliedtoalllinepowermodules:Input Voltage Low Shutdown and
Input Voltage Low Restart.
Whentheinputvoltagefallsbelowthelowshutdownthreshold,thelinepowermoduleswillpoweroffall
outputchannels.Setthisthresholdtoavaluethatpreventsover-dischargeofthebattery.
Whentheinputvoltagerisesabovetherestartthreshold,theunitsturnbackon.Therestartthreshold
mustbeatleasttwovoltsabovetheshutdownthresholdortheLP Module Configuration Error alarm
willactivate(Cordex®HPLPS36linepowermoduleonly).
Thesesettingsarestoredonthelinepowermoduleitselfwhichmeansthatevenifdisconnectedfromthe
controllerthelinepowermoduleswillstillperforminthisway.
To configure the line power modules:
1. GotoSystems > Line Power System > Configure System.
2. IntheConfiguration table,settheInput Voltage Low Shutdown thresholdtothedesiredvalue.
3. Inthesametable,settheInput Voltage Low Restart thresholdtothedesiredvalue.
8.3.1. Shared alarm configuration
TheShared Alarm Configuration featureisasettingwhichcanbeusedtoenable/disableorchange
thepriorityofalarmsonalllinepowermodulesinasystem.Whenusingthisfeatureyoucanconfigure
boththeChannel Shutdown andtheModule Failure alarmsonthespecificlinepowersystembeing
configured.ConfiguringChannel Shutdown willapplythesettingtoeachofthefourchannelshutdown
alarmsoneachlinepowersystemmodule.
Page 116 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish