Cordex®CXCHPControllerSoftwareManual|8-Linepowersystems
1. GotoSystems > Add or Remove Systems andselecttheCreate System button.
2. SelectCreate Line Power System fromthedropdownlist.TheCreate Line Power System
wizardwilllaunch.
3. Namethesystemifrequired.
4. FromtheSelect System Type dropdownlist,selectthevaluethatcorrespondstoyourline
powermoduletype.Iftherearelinepowermodulesalreadyconnectedtothecontroller,theyare
preselectedwiththecorrectoption.
5. Followtherestofthewizardinstructions.
8.2.1. Create a system from a configuration file
Asystemcanbecreatedbyimportingfromaconfigurationfile.SeetheImporting a system sectionfor
moreinformation.
8.3. Configure the line power modules
Therearetwosettingsthatareappliedtoalllinepowermodules:Input Voltage Low Shutdown and
Input Voltage Low Restart.
Whentheinputvoltagefallsbelowthelowshutdownthreshold,thelinepowermoduleswillpoweroffall
outputchannels.Setthisthresholdtoavaluethatpreventsover-dischargeofthebattery.
Whentheinputvoltagerisesabovetherestartthreshold,theunitsturnbackon.Therestartthreshold
mustbeatleasttwovoltsabovetheshutdownthresholdortheLP Module Configuration Error alarm
willactivate(Cordex®HPLPS36linepowermoduleonly).
Thesesettingsarestoredonthelinepowermoduleitselfwhichmeansthatevenifdisconnectedfromthe
controllerthelinepowermoduleswillstillperforminthisway.
To configure the line power modules:
1. GotoSystems > Line Power System > Configure System.
2. IntheConfiguration table,settheInput Voltage Low Shutdown thresholdtothedesiredvalue.
3. Inthesametable,settheInput Voltage Low Restart thresholdtothedesiredvalue.
8.3.1. Shared alarm configuration
TheShared Alarm Configuration featureisasettingwhichcanbeusedtoenable/disableorchange
thepriorityofalarmsonalllinepowermodulesinasystem.Whenusingthisfeatureyoucanconfigure
boththeChannel Shutdown andtheModule Failure alarmsonthespecificlinepowersystembeing
configured.ConfiguringChannel Shutdown willapplythesettingtoeachofthefourchannelshutdown
alarmsoneachlinepowersystemmodule.
Page 116 0350058-J0 Rev AL