Cordex®CXCHPControllerSoftwareManual|6-Convertersystems
Youcanconfiguretheconverteralarmsassociatedwiththesystem.Youcanenableordisablethe
alarms,changethepriority,maprelaystothealarms,andwhereapplicable,modifythethresholds.
To create a converter system:
1. GotoSystems > Add or Remove Systems.
2. SelectCreate Converter System.Namethesystemifrequired.
3. IntheSelect System Type dropdownmenu.
4. Stepthroughtherestofthewizardinstructions.
5. UsetheConfigure Converter System wizardtoconfigurethebasicsystemsettingsandthe
systeminventory.
6.2.1. Creating a system from a configuration file
Asystemcanbecreatedbyimportingfromaconfigurationfile.SeetheImporting a system sectionfor
moreinformation.
6.3. Configure the converters
Thesesettingsincludestartdelay,outputvoltage,orover-voltageprotectionthreshold.
Notice: The output voltage is also the voltage that the converters default to if they lose
communication with the controller. The converters will drop any of the adjustments made by the
controller to perform load sharing and just try to meet the configured output voltage.
Thisfeaturehasatimedelaythatvariesaccordingtoconverters.Mostconvertersreverttooutputmode
afterfiveminutes.Checktheconvertermanualforalistofdefaultparameters.
To configure the converters:
1. GotoSystems > Converter System > Inventory > Converters > Configuration.
2. IntheConfiguration table,setupyourconvertergroupconfigurationsettings.Theseinclude,
System Start Delay andOver-voltage Protection threshold.
3. Configurethesettingsfortheconverters.Thevaluesforthesesettingsdependonyourspecific
system.
6.4. Configure the shunts
Bydefaultthesystemhasnoshunts.Youmayaddorremoveshuntsasneeded.
ToconfigureashuntyouneedanADIOmodulewithcurrentinputs.Theshuntwillmapthecurrentinputs
fromtheADIOmoduletotheLoad Current Source fieldoftheLoad configurationtableortheBattery
Current Source fieldoftheBattery Configuration table.
To configure the shunts: