Cordex®CXCHPControllerSoftwareManual|6-Convertersystems
Youcanconfiguretheconverteralarmsassociatedwiththesystem.Youcanenableordisablethe
alarms,changethepriority,maprelaystothealarms,andwhereapplicable,modifythethresholds.
To create a converter system:
1. GotoSystems > Add or Remove Systems.
2. SelectCreate Converter System.Namethesystemifrequired.
3. IntheSelect System Type dropdownmenu.
4. Stepthroughtherestofthewizardinstructions.
5. UsetheConfigure Converter System wizardtoconfigurethebasicsystemsettingsandthe
systeminventory.
6.2.1. Creating a system from a configuration file
Asystemcanbecreatedbyimportingfromaconfigurationfile.SeetheImporting a system sectionfor
moreinformation.
6.3. Configure the converters
Thesesettingsincludestartdelay,outputvoltage,orover-voltageprotectionthreshold.
Notice: The output voltage is also the voltage that the converters default to if they lose
communication with the controller. The converters will drop any of the adjustments made by the
controller to perform load sharing and just try to meet the configured output voltage.
Thisfeaturehasatimedelaythatvariesaccordingtoconverters.Mostconvertersreverttooutputmode
afterfiveminutes.Checktheconvertermanualforalistofdefaultparameters.
To configure the converters:
1. GotoSystems > Converter System > Inventory > Converters > Configuration.
2. IntheConfiguration table,setupyourconvertergroupconfigurationsettings.Theseinclude,
System Start Delay andOver-voltage Protection threshold.
3. Configurethesettingsfortheconverters.Thevaluesforthesesettingsdependonyourspecific
system.
6.4. Configure the shunts
Bydefaultthesystemhasnoshunts.Youmayaddorremoveshuntsasneeded.
ToconfigureashuntyouneedanADIOmodulewithcurrentinputs.Theshuntwillmapthecurrentinputs
fromtheADIOmoduletotheLoad Current Source fieldoftheLoad configurationtableortheBattery
Current Source fieldoftheBattery Configuration table.
To configure the shunts: