EasyManuals Logo

EnerSys Alpha Cordex CXC HP User Manual

EnerSys Alpha Cordex CXC HP
279 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #101 background imageLoading...
Page #101 background image
Cordex®CXCHPControllerSoftwareManual|6-Convertersystems
Youcanconfiguretheconverteralarmsassociatedwiththesystem.Youcanenableordisablethe
alarms,changethepriority,maprelaystothealarms,andwhereapplicable,modifythethresholds.
To create a converter system:
1. GotoSystems > Add or Remove Systems.
2. SelectCreate Converter System.Namethesystemifrequired.
3. IntheSelect System Type dropdownmenu.
4. Stepthroughtherestofthewizardinstructions.
5. UsetheConfigure Converter System wizardtoconfigurethebasicsystemsettingsandthe
systeminventory.
6.2.1. Creating a system from a configuration file
Asystemcanbecreatedbyimportingfromaconfigurationfile.SeetheImporting a system sectionfor
moreinformation.
6.3. Configure the converters
Thesesettingsincludestartdelay,outputvoltage,orover-voltageprotectionthreshold.
Notice: The output voltage is also the voltage that the converters default to if they lose
communication with the controller. The converters will drop any of the adjustments made by the
controller to perform load sharing and just try to meet the configured output voltage.
Thisfeaturehasatimedelaythatvariesaccordingtoconverters.Mostconvertersreverttooutputmode
afterfiveminutes.Checktheconvertermanualforalistofdefaultparameters.
To configure the converters:
1. GotoSystems > Converter System > Inventory > Converters > Configuration.
2. IntheConfiguration table,setupyourconvertergroupconfigurationsettings.Theseinclude,
System Start Delay andOver-voltage Protection threshold.
3. Configurethesettingsfortheconverters.Thevaluesforthesesettingsdependonyourspecific
system.
6.4. Configure the shunts
Bydefaultthesystemhasnoshunts.Youmayaddorremoveshuntsasneeded.
ToconfigureashuntyouneedanADIOmodulewithcurrentinputs.Theshuntwillmapthecurrentinputs
fromtheADIOmoduletotheLoad Current Source fieldoftheLoad configurationtableortheBattery
Current Source fieldoftheBattery Configuration table.
To configure the shunts:
Page 100 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish