Cordex®CXCHPControllerSoftwareManual|2-Softwarereleasehistory
• AddedanadditionalauthenticationattributeforRADIUSremoteauthentication.
• AddedPreliminaryPolariumbatterysupportfortheDCSystem.Initialsupportmonitorsthe
batteriesonly.
◦ Featurecompatibilityisnotguaranteedinfuturesoftwarereleases.
◦ PowerFlowisnotavailableforthePolariumbattery.
◦ ThePolariumProtocolBridgewillsendmeaninglessvalueswhennobatterymodulesare
connected.Thesecansafelybeignored.
2.3. Application release 7.30
Released: July2022
Containsthefollowingsignificantchanges:
• ImprovedsupportforNiCadbatteries.
• ChangedthemaximumvalueoftheFXMHPUPSKeepAliveStartupDelayto3600seconds.
• AddedanoptiontoturntheFXMHPUPSonautomaticallyafterprogrammedACOutput
Shutdown.
• AddedtheabilitytoshutdowntheFXMHPUPSACoutputvoltageviaSNMPintheUPSMIB.
• ChangedthewayinvalidvaluesareindicatedinSNMP.
• FixedaproblemwiththereportingofupsEstimatedMinRemainingvalueintheUPSMIB.
• AddedmissingControllerInfofieldsintheResourceMIB.
• TheBatteryCurrentSourcefield,forabatterysystem,hashadavailablemappingoptionsreduced.
AnyloadrelatedoptionsandtheTotalOutputCurrentfieldarenolongeravailableformapping.
•
Onupgradetoversion7.30fromanypriorversionofCordex®CXCHPsoftware,ifaDCSystem
BatteryStringhadmappeditsBatteryCurrentSourcetoTotalOutputCurrentthenitwillbeset
to"---"onupgrade.Manualinterventionisrequiredtoupdatethesourcetoeitherabatteryshunt
oracalculation.Thisfixesapotentialproblemwithunintendedbatterydischargeduetoincorrect
batterycurrentconfiguration.
• Asuffixhasbeenaddedtothenameexportedconfigfilestodistinguishbetweenclone,system/
ADIO,andpartial.
• TotalOutputCurrentfieldforaDCSystemhasbeenrenamedtoTotalRectifierO/PCurrent.
• OnaChangeRelayaction,theRelayToChangeentrynolongerrequiresanexclusiverelay;the
chosenrelaycannowbesharedwithotheralarms.
2.4. Application release 7.20
Released: January2022
Containsthefollowingsignificantchanges:
0350058-J0 Rev AL Page 21