Cordex®CXCHPControllerSoftwareManual|19-Maintainingthesystem
Change the system configuration
Oncethesystemhasbeencreated,mostofthesystemconfigurationcannotbechanged.Thenumberof
phases,numberofDCgroups,andnumberofACgroupscannotbechanged.Ifanyofthesevaluesare
incorrecttheinvertersystemmustbere-commissionedandallinvertersunplugged.
Add or remove inverters
Ifmoreinvertersareneededtoincreasecapacity,theAdd Inverters wizardguidesusersthroughthis
process.
Important: To ensure the T2S system is configured correctly, it is necessary to use these wizards
to add or remove inverters from the system. This ensures that the correct number of inverters,
and the correct number of redundant modules in each phase. This is important for the operation
of T2S system alerts and alarms.
GotoSystems > Inverter System > Inventory > Inverters > Status toaccesstheAdd Inverters
wizard.
Ifinvertersmustberemovedfromthesystem,usetheRemove Inverters wizard.GotoSystems >
Inverter System > Inventory > Inverters > Status toaccesstheRemove Inverters wizard.
19.2.1. Maintenance bypass
ForsystemconfigurationsthatuseageneratorfortheACinput,thesafestwaytoinitiateamaintenance
bypassistofollowtheinstructionsintheInitiate Zero Phase Shift wizard.Thiswizardshouldbeused
whenevertheinvertersystemhastobeputintoortakenoutofbypass.Thispreventstheinvertersfrom
turningoffwhenthebypassswitchbrieflyshort-circuitstheACinputandoutput.
GotoSystems > Inverter System > System Functions > Zero Phase Shift toaccesstheInitiate Zero
Phase Shift wizard.
ThewizardshiftsthephaseandvoltageoftheACoutputtomatchtheinput.
19.2.2. Taking power from DC source
TheinvertersystemcantakepowerfromtheDCsource(usuallybatteries)underthreeconditions:
1.
ACmainsislost;
2.
ManualDCpriorityisenabled;
3.
Inputpowerlimitisenabled.
WhenACmainsislost,theinverterswillalwaystakepowerfromtheDCsourceifavailable.
Page 168 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish