Cordex®CXCHPControllerSoftwareManual|19-Maintainingthesystem
Change the system configuration
Oncethesystemhasbeencreated,mostofthesystemconfigurationcannotbechanged.Thenumberof
phases,numberofDCgroups,andnumberofACgroupscannotbechanged.Ifanyofthesevaluesare
incorrecttheinvertersystemmustbere-commissionedandallinvertersunplugged.
Add or remove inverters
Ifmoreinvertersareneededtoincreasecapacity,theAdd Inverters wizardguidesusersthroughthis
process.
Important: To ensure the T2S system is configured correctly, it is necessary to use these wizards
to add or remove inverters from the system. This ensures that the correct number of inverters,
and the correct number of redundant modules in each phase. This is important for the operation
of T2S system alerts and alarms.
GotoSystems > Inverter System > Inventory > Inverters > Status toaccesstheAdd Inverters
wizard.
Ifinvertersmustberemovedfromthesystem,usetheRemove Inverters wizard.GotoSystems >
Inverter System > Inventory > Inverters > Status toaccesstheRemove Inverters wizard.
19.2.1. Maintenance bypass
ForsystemconfigurationsthatuseageneratorfortheACinput,thesafestwaytoinitiateamaintenance
bypassistofollowtheinstructionsintheInitiate Zero Phase Shift wizard.Thiswizardshouldbeused
whenevertheinvertersystemhastobeputintoortakenoutofbypass.Thispreventstheinvertersfrom
turningoffwhenthebypassswitchbrieflyshort-circuitstheACinputandoutput.
GotoSystems > Inverter System > System Functions > Zero Phase Shift toaccesstheInitiate Zero
Phase Shift wizard.
ThewizardshiftsthephaseandvoltageoftheACoutputtomatchtheinput.
19.2.2. Taking power from DC source
TheinvertersystemcantakepowerfromtheDCsource(usuallybatteries)underthreeconditions:
1.
ACmainsislost;
2.
ManualDCpriorityisenabled;
3.
Inputpowerlimitisenabled.
WhenACmainsislost,theinverterswillalwaystakepowerfromtheDCsourceifavailable.
Page 168 0350058-J0 Rev AL