Cordex®CXCHPControllerSoftwareManual|13-Cordex®CXPS-HSSHyperboostconvertersystem
To configure the shunts:
1. GotoSystems > Converter System > Inventory > Shunts.Youwillseealistofshuntsinthe
system.Addorremoveshuntsfromthispage.
2. SelecttheGO TO buttonfortheshuntyouwanttoconfigure.
3. IntheConfiguration table,assigntheshuntanameanddescription.Werecommendthatyou
assigntheshuntanamethatrepresentstheactualshunt.ForexampleyoumightnameitBattery
Shunt.
4.
SelecttheShunt Current Source.
ThisisthecurrentinputonanADIOmodulethattakesavoltagereadingacrosstheshunt.
5. EntertheRange in Amps fortheshunt.
6. EntertheRange in Millivolts fortheshunt.
7. EntertheOffset Calibration fortheshuntiftheshuntreadingerroristooloworhigh.
13.5. Configure the loads
Bydefaultthesystemhasoneload.Youmayaddorremoveloadsasneeded.
To configure the loads:
1. GotoSystems > Converter System > Inventory > Loads.Youwillseealistofloadsinthe
system.Addorremoveloadsfromthisscreen.
2. SelecttheGO TO buttonfortheloadyouwanttoconfigure.
3. IntheConfiguration table,assigntheloadanameandadescription.Werecommendthatyou
assigntheloadanamethatrepresentstheactualload.
4.
SelecttheLoad Voltage Source.ThisisthevoltageinputonanADIOmodulethattakesavoltage
readingneartheload.
Ifyoudonothaveasensorconnected,youmaywanttoselecttheAverage Converter Output
Voltage.
5.
SelecttheLoad Current Source.Thisistheshuntinputthatreadstheloadcurrent.Ifyouhave
arealshuntreadingfortheloadcurrent,thenselecttheshuntfromthedropdownlist.Ifyoudon't
seetheshuntyouwant,thencreateit.
Ifyoudonothaveashuntforreadingtheloadcurrent,youmaywanttoselecttheTotal Output
Current fortheconvertersystem.
6.
SelecttheEDIT buttonfortheLoad Breaker/Fuse Source.SelectthedigitalinputontheADIO
modulewhichisconnectedtomonitorthebreakerorthefuse.
IfyouneedtochangethepolarityfortheLoad Breaker/Fuse Open alarm,gototheModules
page,fromtheAll Modules table,selecttheADIOmodulerequired,andthenselecttheGO TO
buttontoaccesstheDigital Inputs table.
7. Configuretheloadalarms.
Page 142 0350058-J0 Rev AL