Cordex®CXCHPControllerSoftwareManual|13-Cordex®CXPS-HSSHyperboostconvertersystem
To configure the shunts:
1. GotoSystems > Converter System > Inventory > Shunts.Youwillseealistofshuntsinthe
system.Addorremoveshuntsfromthispage.
2. SelecttheGO TO buttonfortheshuntyouwanttoconfigure.
3. IntheConfiguration table,assigntheshuntanameanddescription.Werecommendthatyou
assigntheshuntanamethatrepresentstheactualshunt.ForexampleyoumightnameitBattery
Shunt.
4.
SelecttheShunt Current Source.
ThisisthecurrentinputonanADIOmodulethattakesavoltagereadingacrosstheshunt.
5. EntertheRange in Amps fortheshunt.
6. EntertheRange in Millivolts fortheshunt.
7. EntertheOffset Calibration fortheshuntiftheshuntreadingerroristooloworhigh.
13.5. Configure the loads
Bydefaultthesystemhasoneload.Youmayaddorremoveloadsasneeded.
To configure the loads:
1. GotoSystems > Converter System > Inventory > Loads.Youwillseealistofloadsinthe
system.Addorremoveloadsfromthisscreen.
2. SelecttheGO TO buttonfortheloadyouwanttoconfigure.
3. IntheConfiguration table,assigntheloadanameandadescription.Werecommendthatyou
assigntheloadanamethatrepresentstheactualload.
4.
SelecttheLoad Voltage Source.ThisisthevoltageinputonanADIOmodulethattakesavoltage
readingneartheload.
Ifyoudonothaveasensorconnected,youmaywanttoselecttheAverage Converter Output
Voltage.
5.
SelecttheLoad Current Source.Thisistheshuntinputthatreadstheloadcurrent.Ifyouhave
arealshuntreadingfortheloadcurrent,thenselecttheshuntfromthedropdownlist.Ifyoudon't
seetheshuntyouwant,thencreateit.
Ifyoudonothaveashuntforreadingtheloadcurrent,youmaywanttoselecttheTotal Output
Current fortheconvertersystem.
6.
SelecttheEDIT buttonfortheLoad Breaker/Fuse Source.SelectthedigitalinputontheADIO
modulewhichisconnectedtomonitorthebreakerorthefuse.
IfyouneedtochangethepolarityfortheLoad Breaker/Fuse Open alarm,gototheModules
page,fromtheAll Modules table,selecttheADIOmodulerequired,andthenselecttheGO TO
buttontoaccesstheDigital Inputs table.
7. Configuretheloadalarms.
Page 142 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish