Cordex®CXCHPControllerSoftwareManual|2-Softwarereleasehistory
2.19. OS release 5.20
Released: March2019
Containsthefollowingsignificantchange:ChangedRAMtimingsforbettercompatibilitywithdifferent
RAMchips.
2.20. OS release 4.70
Released: February2019
Containsthefollowingsignificantchanges:
Improvedflashprogrammingreliability
AddedfeaturetoallowapplicationtostartaflashrefreshforflashusedbyOS
SupportforVLAN
Fixforclockoverflow
2.21. OS release 2.20
Released: August2015
Containsthefollowingsignificantchange:Supportin-shelfcontrollerproduct
2.22. Known issues
TheDefaultPowerFlowandDefaultDashboardsettingshavebeenobsoletedandnolong
appearsonthewebinterface.Thesesettingsareincompatiblewiththenewwebinterfacemenu
navigation.
Ifusingapplicationversion7.10onanin-shelfcontroller(forexample,Cordex®CXCM1HP
controller),thebackup,restore,andapplicationupgradefeaturesviaapluggedinUSBdrive
willnotsucceed.Pleaseupgradetoapplicationversion7.20viaawebbrowsertorestorethis
functionality.
Forapplicationversionspreviousto7.10,ifarestoreisinitiatedanditfails,itisrecommendedto
restartthecontrollerandattempttherestoreagain.
Forapplicationversions6.30,7.00,and7.01,iftheDNSaddressorGatewayaddressforan
ethernetportissetto0.0.0.0thenanOSupgradecouldcausetheethernetconfigurationtonot
resynconstartup.TheDNSaddressorGatewayaddressshouldbefilledinwithacorrectaddress
orleftblank.
Ifamodulehasanalertwhenitisfirstpoweredon,thealertwillnotappearinthealertlog.Itwill,
however,beshowninthemodulesactivealerttable.
Inversion6.00,onsystemswithhighvoltagerectifiers(except125V/4.4kW),aRectifier
ConfigurationErroralarmwilloccur.Thisalarmcannotbecleared.Upgradetoversion6.10,or
downgradetoversion5.21orearliertosolvethisproblem.
0350058-J0 Rev AL Page 27

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish