Cordex®CXCHPControllerSoftwareManual|2-Softwarereleasehistory
2.19. OS release 5.20
Released: March2019
Containsthefollowingsignificantchange:ChangedRAMtimingsforbettercompatibilitywithdifferent
RAMchips.
2.20. OS release 4.70
Released: February2019
Containsthefollowingsignificantchanges:
• Improvedflashprogrammingreliability
• AddedfeaturetoallowapplicationtostartaflashrefreshforflashusedbyOS
• SupportforVLAN
• Fixforclockoverflow
2.21. OS release 2.20
Released: August2015
Containsthefollowingsignificantchange:Supportin-shelfcontrollerproduct
2.22. Known issues
• TheDefaultPowerFlowandDefaultDashboardsettingshavebeenobsoletedandnolong
appearsonthewebinterface.Thesesettingsareincompatiblewiththenewwebinterfacemenu
navigation.
• Ifusingapplicationversion7.10onanin-shelfcontroller(forexample,Cordex®CXCM1HP
controller),thebackup,restore,andapplicationupgradefeaturesviaapluggedinUSBdrive
willnotsucceed.Pleaseupgradetoapplicationversion7.20viaawebbrowsertorestorethis
functionality.
• Forapplicationversionspreviousto7.10,ifarestoreisinitiatedanditfails,itisrecommendedto
restartthecontrollerandattempttherestoreagain.
• Forapplicationversions6.30,7.00,and7.01,iftheDNSaddressorGatewayaddressforan
ethernetportissetto0.0.0.0thenanOSupgradecouldcausetheethernetconfigurationtonot
resynconstartup.TheDNSaddressorGatewayaddressshouldbefilledinwithacorrectaddress
orleftblank.
• Ifamodulehasanalertwhenitisfirstpoweredon,thealertwillnotappearinthealertlog.Itwill,
however,beshowninthemodulesactivealerttable.
• Inversion6.00,onsystemswithhighvoltagerectifiers(except125V/4.4kW),aRectifier
ConfigurationErroralarmwilloccur.Thisalarmcannotbecleared.Upgradetoversion6.10,or
downgradetoversion5.21orearliertosolvethisproblem.
0350058-J0 Rev AL Page 27