Cordex®CXCHPControllerSoftwareManual|2-Softwarereleasehistory
Inversion4.10,theSNMPtrapvarbindscontrollerInfoName andalarmSeverity swapped
position.Thiswasremediedinversion4.20sothatthevarbindsmatchthepositionasspecifiedin
theMIBastheydidinversionspreviousto4.10.
WhenusingaMIBbrowsertoreadcontrollerdatathatrepresentsastate,thenumericvalueofthe
stateismovedtothedataNumberValuecolumn(fromthedataStringValuecolumn)andit’sstring
valueisnowshowninthedataStringValuecolumn.
Downgradingcontrollersoftware
Downgradingthecontrollersoftwareshouldbearareoccurrence.Whensoftwareis
downgraded,anyconfigurationsettingsforfeaturesthatdon'texistinearlierversionsare
discarded.Becausesomeconfigurationsarediscarded,thecontrollermayrequiremanual
interventiontoensureeverysettingiscorrect.Restoringabackupfilethatwasmadewith
theearlierversionofsoftwareisrecommendedinstead.
Inversions2.Xand3.Xofthesoftware,wefoundtwoissues.Thefirstisthatwhenthe
softwareencounteredaninverterordistributionsystemthatitdidn'tunderstand,the
softwarediscardedmoredatathanexpected.Thesecondisthatwhenacustomdata
variablehaddatadiscarded,thecontrollerwouldcrashandnotrecover.
Ifadowngradefromversion4.00softwarebecomesanecessity,youcanavoidthese
problemsbydeletingallinvertersystems,distributionsystems,andallcustomdatabefore
performingthedowngrade.
Importingconfigurationfilesfromlaterversionstoearlierversionsmayfail-especiallyifthe
controllerisrunningaversionprevioustoversion4.00.Iftheimportfailsifmaybebecauseit
containsnewsystemsorcustomdatathatusesvariablevaluesthatdonotexist.Tryimporting
usingaconfigurationfilethatdoesn'tcontaininvertersystems,distributionsystems,orcustom
data.
Importingconfigurationfilesfromearlierversionstolaterversionscanhavesomequirks.
Controllerfeatureswhichdidnotexistintheearlierversionwillnothaveanysettingssavedinthe
configurationfilesexportedfromthoseearlierversions.Therefore,anyconfigurationofthesenew
featuresontheControllerwillnotbeoverwrittenbytheoldconfigurationfile.Ifaconfigurationfile
whichsetsthesefeaturesbacktotheirdefaultsisdesired,itmustbeexportedfromaversionin
whichthefeaturesexist.
FileuploadworksinthecurrentversionofMicrosoftEdge,InternetExplorer,GoogleChrome,
MozillaFirefox,andAppleSafari.FileuploaddoesnotworkinInternetExplorer9.IfusingInternet
Explorer9,youcannotuploadtheCordex®CXCHPcontrollerapplicationupgradeortheACAN
filesforCANmoduleupgrades.
CounterandtimervaluesintheCounters andTimers tablesfoundunder
ControllerProgrammabilityCustom Datadonotpersist,theyreverttotheirdefaultvaluesona
restart.
TheLCDdoesnotcurrentlysupportaccentedcharactersforpasswordsoraliases.
Page 28 0350058-J0 Rev AL