Cordex®CXCHPControllerSoftwareManual|21-Maintainingmodules
1. GotoModules andselecttheGO TO buttononthedevicewithTemperature Sensors.
2. IntheAlarms tablethereisonealarmforeachtemperaturesensorontheADIOmodule.Select
theGO TO buttontoenableordisablethealarmfortherequiredsensor.
3. Assignarelayoranyotherparametersasrequired.
21.1.8. Ground fault detection
GroundfaultdetectionisavailableontheCordex®CXCHPHV-ADIOsmartperipheral.
21.1.8.1. Cordex® CXC HP HV-ADIO ground fault detection
TheCordex®CXCHPHV-ADIOperipheralhasagroundfaultdetection(GFD)feature,underthe
Modules > HV-ADIO menuintheConfiguration table,whichcanbeenabledordisabled.Itisdisabled
bydefault.
Whendisabled,thetworelatedvalues(GFDResistanceandGFDCurrent)readUnknown,andnoGFD-
relatedalarmsaretriggered.ThesevaluesarefoundundertheGFD Information table.
Whenenabled,theresistanceandcurrentacrosstheGFDcircuitisreportedundertheGFD Information
table.TherearetwoalarmsrelatedtotheGFDlocatedintheAlarms tableoftheCordex®CXCHPHV-
ADIOperipheral.
Ground Fault Resistance Low alarmwillberaisediftheresistanceislowerthantheconfigurable
threshold,whichis20000ohmsbydefault.
Ground Fault Current High alarmwillberaisedifthecurrentishigherthantheconfigurable
threshold,whichis1mAbydefault.
21.2. Module firmware upgrades
ThissectioncovershowtoupgradethefirmwareonCANdevicesattachedtothecontroller.
21.2.1. Module firmware upgrade
Toupgradethefirmwareonamodule,gotoModules thengotoFirmware Upgrade tablefromeitherthe
webinterfaceortheLCD.
21.2.2. Upload a firmware file
Upload a firmware file from the LCD
FromtheLCDyoucaneitherchooseafileuploadedfromaUSBdriveoronefromtheLocal Files folder.
TheLocal Files menucontainsalistoffilespreviouslyuploadedviathewebinterface.GotoMenu >
Modules > Firmware Upgrade > File.
0350058-J0 Rev AL Page 231

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish