Cordex®CXCHPControllerSoftwareManual|19-Maintainingthesystem
TheLast Battery Test Error Condition shouldhavethevalue:None.
AremotebatterytestisstartedwhentheTrigger Input goesfromInactive toActive.
AremotebatterytestisnormallyterminatedwhentheTrigger Input goesfromActive toInactive.
Asasafetymeasure,thebatteryalsoterminatesifthevoltagedropsbelowtheterminationvoltage
thresholdorthetesttimesout.
19.4.4. Battery temperature compensation
ToviewthebatterytemperaturecompensationgotoSystems > DC System > System Functions >
Temperature Compensation > Status.NotethatyoumusthaveabatterydefinedintheDCSystemin
ordertohavethismenuitemavailableunderSystem Functions.
Batterytemperaturecompensationusesthetemperatureprobesconnectedtothetemperatureinputson
theADIOmoduleswhicharepartofthesystem.Thisfeaturewillnotfunctionoptimallyiftheseprobesare
damagedordisconnectedfromthesystem.
ToviewthevaluesofthetemperatureinputsgotoModules,IntheCAN Modules tableselecttheADIO
modulesthathavebatterytemperatureprobesattached.Confirmallprobesareworkingcorrectlyandthe
temperaturesarereasonable.
19.5. Low voltage disconnect (LVD) maintenance
Lowvoltagedisconnects(LVDs)areusedtodisconnectloadsorthebatteryduringlowvoltageconditions.
WhenanLVDactivates,thesystemdisplaysanalarmandamessage.Therecanbeadeepdischarge
ofthebatteriesduringanACfail.Dischargingthebatterytoanextremelylowvoltagecancausedamage
totheloadandtothebattery.TheLVDisusedtodisconnectthebattery,oroneormoreloadsduring
extremelylowvoltageconditionstoavoiddamagetotheloadorthebattery.OnceACpowerreturns,and
thelowvoltageconditionnolongerexists,theLVDautomaticallyreconnectstheloads.
Disconnectsallowyoutoprogramanumberofdifferentdisconnectorconnectconditions.Creating
multipleLVDcontrolsprovidesthecapabilityofloadshedding,whichmeanstheleastcriticalloadsare
disconnectedfirst.
ConditionsthatcouldtriggeranLVDareasfollows:
Disconnectatdisconnectvoltagethreshold;connectatconnectvoltagethreshold.
DisconnectattimeafterACFail;connectatconnectvoltagethreshold.
DisconnectwhenBatterySOCfallsbelowathreshold;connectwhenSOCisfivepercentabove
theSOCthreshold.
0350058-J0 Rev AL Page 177

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish