Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
WhenviewedontheLCD,thelogshowsstarttime,endtime,andtimeanddurationofeachpower
outage.
Whenviewedonthewebinterface,thelogincludesthesystemID,starttime,endtime,anddurationof
eachpoweroutage.
WhenexportedtoaCSVfile,thelogincludesthesystemID,starttime,endtime,anddurationofeach
poweroutage.
20.4.4. Datalogs
Datalogs allowsuserstorecordmeasurements(Data Signals)atsetintervalsoveraperiodoftime.The
Datalog usesthecontrollersensorsandcalculatedvaluesasinputs.Thecontrollersupportsuptoten
Datalogs,eachofwhichmayberecordingupto20Data Signals.
Theintervalbetweensamplescanbeconfigured,aswellasthenumberofsamplescollected.Whenthe
maximumnumberofsampleshavebeencollected,thenewestsamplereplacestheoldestsample.Data
capturecaneitherbestartedandruncontinuouslyoranequationcanbeusedtocontroldatacapture.
Datalogsaresavedtothefilesystemwhenthecontrollerisresetbyauser,aswellasbeingautomatically
savedonceeveryday.Ifpowerislosttothecontroller,thereispotentialforsomedataloss.
IfanyData Signals arenotconfigured,aDatalog willnotstart.
IfthereisaClock Error Alarm—whichmeansthatthedatehasnotbeenset,aDatalog willnotstart.
IfaDatalog isrunningandacontrollerresetoccurs,theDatalog willtrytoresumedatacollectionon
controllerstartup.
Ifthereisdataavailable,aPreview Chart displaysupto30samples.IftherearemorethanfiveData
Signals,onlythefirstfivesignalsaredisplayedinthepreview.Ifavalueisunknown,itisdisplayedon
thepreviewasazerovalue.
20.4.4.1. Create a datalog
TherearethreestagestosettingupaDatalog:
AddaDatalog
AddtheData Signals
RuntheStart Capture command
TocreateaDatalog:
1.
GotoLogs > Datalogs andselectAdd Datalog.
Uptotendatalogscanbecreated.
2. SelecttheGO TO buttonofthenewDatalog.
Page 194 0350058-J0 Rev AL