Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
3. FromtheConfiguration table,selecttheEDIT buttontosetupthefollowinginformation:
a. Name: TheDatalogname.
b. Description: DescribethepurposeorusageoftheDatalog.
c. Number Of Samples To Capture: From60to3600samples.
d. Sampling Method:
Datalogs canbeconfiguredtoeitherSample at Fixed Time Intervals,orSample on
Trigger Data Signal Change inwhichcaseanewsampleofallDataSignalswillbe
takenonlywhentheTrigger Data Signal changesbymorethantheTrigger Data Signal
Deadband comparedtoitsvaluewhentheprevioussamplewastaken.
e. Sample Interval: Settheintervalfrom2secondsto3hours(10800seconds).
f. Trigger Data Signal: TheDataSignalwhichtriggerssampling,whentheSamplingMethod
issettoSampleonTriggerDataSignalChange.
g. Trigger Data Signal Deadband: DetermineshowmuchtheTrigger Data Signal hasto
changebeforeanewsampleistaken.
h.
Capture When True: Controlswhetherdataiscapturedcontinuouslyoronlyundercertain
conditions.
IftheCapture When True valuegoesunknown,theDatalogwillignoreit.IftheDatalog
isinthewaitingstate(orthesamplingstate),whentheCapture When True valuegoes
unknown,theDatalogwillstayinitscurrentstate,eitherwaiting(orsampling)state.
4.
FromtheData Signals table,selectAdd Data Signal toaddthenumberofdatasignalsyouneed.
Upto20signalscanbecreated.
5.
FromtheConfiguration table,selecttheEDIT buttontosetupthefollowinginformationforeach
Data Signal:
a. Name: Thesignalname.
b. Description: Documentwhatthesignalmeansorhowitsvalueshouldbeinterpreted.
c. Field: BringupthefieldpickerandselecttheADIOmoduleinputorothervalueyouwantto
monitor.
Youcannotleavedatasignalfieldsunknown.Youcannotselectstateorbooleanvaluesfor
datasignals.
6.
RuntheStart Capture command.
IfalloftheData Signals arenotconfiguredwhentheStartCapturebuttonispressed,thecapture
willstillstart,butanentryismadeintheeventlogtoindicateaDataSignalisnotconfigured.
0350058-J0 Rev AL Page 195

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish