Cordex®CXCHPControllerSoftwareManual|7-Invertersystems
Thesearebrieflydescribedinthefollowingsection.Forinformationonusingthesefunctionsgothe
Inverter & T2S System Maintenance section.
Zero phase shift
Theoutputoftheinvertersisnormallyshiftedfromtheinputbyfivedegreesforcertainregulatory
compliance.Forsomesystemsrunningongenerator,itmaybenecessarytomomentarilyreducethis
phaseshifttozerodegreesbeforeanymanualbypassoperationisperformed.Awizardguidesyou
throughthisoperation.
Duringthewizard,thecontrollerwillcheckthedifferencebetweentheinputvoltageandoutputvoltage
(asmeasuredline-neutral).Thisdifferenceiscausedbydifferentlevelsofloadingoninputoroutputor
unusualACmainsconditions.Ifthedifferenceisgreaterthan6volts,awarningindicatesthatproceeding
withthebypassoperationmayresultinmomentaryinterruptionofpowertotheload.Ifthedifference
islargerthan6voltsthereisasmallchancethatinvertersmayshutdownwhentheydetecttoomuch
currentflowingintotheinputoroutputasthebypassswitchisturned.Ifthiswarningisoccurs,waituntil
inputandoutputareclosertogether.
AC input power limit
ThisfunctioncanbeusedtolimittheACinputpowerthattheinvertersystemwilltakebyusingsomeof
theenergyfromaDCbus.Ifthereisonlyabattery(andnorectifiers)supplyingtheDCbus,thisfunction
mustbemanuallycontrolledbyanoperatortoensurethebatteryisrechargedonceitisdepleted.
Manual DC priority
ThisfunctioncanbeusedtotakepowerfromtheDCbusbasedanonauser-specifiedpercentage.If
thereisonlyabattery(andnorectifiers)supplyingtheDCbus,thisfunctionmustbemanuallycontrolled
byanoperatortoensurethebatteryisrechargedonceitisdepleted.
7.2. Create an inverter system
There are two options for creating an inverter system:
UsetheCreate System wizardviatheSystems > Add or Remove Systems menu,andselect
Create Inverter System fromthedropdownmenuofsystemstocreate.
Useaconfigurationfiletoimportaninvertersystem.
Afteraninvertersystemiscreated,itmusthaveoneT2Smoduleassignedtoit.TheT2Smoduleisa
CANdevicethatcontrolsandmonitorstheinverters.
7.2.1. Create a system from a configuration file
Asystemcanbecreatedbyimportingfromaconfigurationfile.SeetheImporting a system sectionfor
moreinformation.
0350058-J0 Rev AL Page 107