Figure 8-4 Anon-filledsortedlinepowerchannelsCSVfile
1. Column cells that should not be changed in the CSV file
TheShelf,Slot,andChannelcolumnsshouldnotbemodifiedastheyarethepossibleconnectionvalues
onthesystemwhichwillbeassignedtoalinepowerload.Thesevaluesareautomaticallypopulated
whenthelinepowerchannelstemplateisusedorthechannelsfileisexported.
a.TheShelf columncorrespondstotheshelfwhichthelinepowermoduleisinserted.
b.TheSlot columncorrespondstotheslotontheshelfthatthelinepowermoduleisinserted.
c.TheChannel columncorrespondstothechannelintheslotthatthelinepowermoduleisinserted.
d.TheModule columnwillbeemptyifthelinepowerchannelstemplateisusedanditwillbefilledinwith
themoduleserialnumberifthechannelsfilewasexportedfromthecontroller.
2. Column cells which are recommended to be changed in the CSV file
AllrecommendedentrieswillbeimportedifavalueisenteredintheCSVcellassociatedwiththeline
powerchannelbutwillnotaffectchanneltolinepowerloadassignment.
a.TheChannel Name canbeenteredwithasuitablename.
b.TheChannel Description canbeenteredwithasuitabledescription.
c.TheLoad Description canbeenteredwithasuitabledescription.
d.Downstream Loads thatarelinkedtoalinepowerloadcanbeentered.Thedownstreamloadsare
basedontheLoad Name. IftheLoad Name,isthesameformultiplechannelsthedownstreamloads
entrymustbethesameaswell.
Anexampleofadownstreamloadisaradiopoweredbyalinepowerdown-converter.Thedown-
convertercanbemadetobethelinepowerloadinthelinepowersystem.Therecanbemanyradioloads
linkedtoonelinepowerload(down-converter)whichprovidestheflexibilitytoenterthosenamesinto
Downstream Loads column.
3. Column cells that is required to be modified in the CSV file
TocreatealoadandassignachanneltoaLoad,theLoad Name mustbeenteredforeachchannel
Page 122 0350058-J0 Rev AL