Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
5.4.1. Represent a converter system as a DC load
AconvertersystemisrepresentedonaDCSystemlikeanordinaryDCload.
To configure a converter system as a DC load:
1. GotoSystems > DC System > Inventory > Loads.Youwillseealistofloadsinthesystem.Add
orremoveloadsfromthisscreen.
2. SelecttheGO TO buttonfortheloadyouwanttoconfigure.
3. IntheConfiguration table,assigntheloadanameandadescription.Werecommendthatyou
assigntheloadanamethatrepresentstheactualload.
4.
SelectLoad Voltage Source.ThisvoltageistheDCinputtotheConverterSystem.Thisis
normallyavoltageinputonanADIOthatmeasurestheDCsystemvoltage.
Ifyoudonothavethisconnected,youcanselecttheinputthatreadsthebatteryvoltageorsystem
voltage.
5. SelectLoadCurrentSource.ThisisnormallytheConverter System > Total Input Current value.
6. Configuretherelatedloadalarms.
5.4.2. Represent an inverter system as a DC load
AninvertersystemwillnormallyhaveanACinputandaDCinput.Theinvertersystemmayonlybeusing
theDCinputwhentheACinputhasfailed.WhentheACinputisavailable,theinvertermaytakeallofits
powerfromtheACinput.
Onthecontroller,invertersystemscanmeasuretheDCcurrenttheyareusingandtheycanalso
calculatehowmuchDCcurrenttheyareexpectingtouse,shouldtheirACinputfail.TheDCSystemuses
bothofthesevaluestocalculatethebatteryruntimeremaininginallsituations.
To configure an inverter system as a DC load:
1. GotoSystems > DC System > Inventory > Loads.Youwillseealistofloadsinthesystem.
2. SelecttheAdd Inverter System Load buttontheLoads tabletoaddanewloadtothelist.
3. SelecttheGO TO buttonfortheloadyouwanttoconfigure.
4. IntheConfiguration table,assigntheloadanameandadescription.Werecommendthatyou
assigntheloadanamethatrepresentstheactualload.
5.
SelecttheLoadVoltageSource.ThisvoltageistheDCinputtotheInverterSystem.Thisis
normallyavoltageinputonanADIOthatmeasurestheDCSystemvoltage.
Ifyoudonothavethisconnected,youcanselecttheinputthatreadsthebatteryvoltageorsystem
voltage.
6. SelecttheLoad Current Source.ThisisnormallytheInverter System > DC Input Current value
whichismeasuringhowmuchDCcurrenttheinvertersystemisusingrightnow.
Page 96 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish