Cordex®CXCHPControllerSoftwareManual|24-Cordex®CXCHPcontrollerreferenceguide
Table 24-4 48voltsystemdefaultvaluesandranges(continued)
Setting name Default Minimum Maximum
TempCompVoltageWarning 1 0 1
BatteryTestTerminationVoltage 44.5 44.5 52
OutputVoltageHighAlarm 55.5 42 60
OutputVoltageVeryHighAlarm 56.5 42 60
OutputVoltageLowAlarm 48 42 60
OutputVoltageVeryLowAlarm 46.5 36 60
24.3.4. 125 volt system default values and ranges
Thistableprovidesthedefaultvaluesandrangesfora125voltsystem.
Table 24-5 125voltsystemdefaultvaluesandranges
Setting name Default Minimum Maximum
AllowedVoltageRange N/A 90 160
FloatVoltage 140.625 90 160
EqualizeVoltage 143.23 90 160
BoostVoltage 143.23 90 160
Rectifier-MinimumTestVoltage 114.58 90 160
SafeVoltage 133.85 90 160
OverVoltageProtection 151.04 90 160
AbsorptionVoltage 143.23 90 160
AbsorptionArmingVoltage 125 90 160
TempCompMaxVoltage 144.53 N/A 160
TempCompMinVoltage 136.72 90 N/A
BatteryStringNumberofCells 63 1 200
TempCompVoltageWarning 2.6 0 2.6
BatteryTestTerminationVoltage 115.89 90 160
OutputVoltageHighAlarm 144.53 90 160
OutputVoltageVeryHighAlarm 147.14 90 160
OutputVoltageLowAlarm 125 90 160
OutputVoltageVeryLowAlarm 121.09 93.75 160
Page 276 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish