Cordex®CXCHPControllerSoftwareManual|14-Generator
6. SelectthePhase foryourAC Source.SelectNext.
7. IntheAlarms page,selectwhethertheACInputFailalarmshouldbeenabledforthissource.
SelectYes orNo.
8. IntheVoltage Readings page,selectthesystemfromwheretheACsourcewillobtainits
readings.
9. ReviewyoursettingsandselectNext.
10. IntheResults step,therewillbeanoptiontolaunchtheConfigure Generator Control wizard.
Alternatively,thiswizardcanbelaunchedfromtheGenerator Control tablewithinthedetailsof
thenewlegacyACgeneratorsource.
14.8.2. Create a legacy DC generator
To create a legacy DC generator:
1. IfaDCsourcesystemdoesnotalreadyexist,createitatSystems > Add or Remove Systems
andlaunchtheCreate System wizard
2. GotoSystems > DC Source System > DC Sources.
3. IntheDC Sources table,selectAdd Legacy DC Generator.
4. AfterthelegacyDCgeneratorhasbeenadded,selecttheGO TO button.Fromhere,thegenerator
controlandalarmscanbeconfigured.
14.8.3. Configure legacy generator control
Frominsidethelegacygenerator:
1. IntheGenerator Control table,selecttheConfigure Generator Control buttontolaunchthe
configurationwizard.
2.
IntheGenerator Control dropdownmenuchoosefromthefollowing:
◦ Enabled: Choseenabledifthegeneratorcanbecontrolledbyarelay.
◦ Disabled: Ifdisabledischosennofurtherconfigurationisrequired.
3. UnderGenerator Control Signals selecttheGenerator Control Relay andtheGenerator
Status Signal Source.SelectNext.
Notice: The Generator Control Relay is mandatory as it is the relay that will be used to
start and stop the generator. This relay can also be driven by other features like alarms.
This provides maximum flexibility in generator control, but requires extra caution to ensure
this generator relay is shared only when intended.
Notice: The Generator Status Signal Source is optional, but it should be mapped to a
digital input which can be used to monitor whether or not the generator is running.
4.
UnderVoltage to Monitor,chooseavoltagesignaltobemonitored.
Page 154 0350058-J0 Rev AL