Cordex®CXCHPControllerSoftwareManual|14-Generator
Notice: The Manual Generator Stop button can be pressed When the Generator State is
Running and waiting for generator to run for minimum runtime or Running and waiting
for Call to Stop to be true. The generator is already stopped when the Generator State shows
disabled or suspended.
TheGenerator State showsDisabled iftheGenerator Control issettoDisabled. Themapped
Generator Control Relay willnotbeenergizedinthisstate.
TheGenerator State canalsoshowsuspendedduetoaconfigurationerror.Thefollowingareall
possiblesuspendedstatesalongwithrecommendationstogetoutofthesuspendedstate:
Suspended - No Relay Mapped: SelectarelaywhichcontrolsthegeneratorintheGenerator
Control Relay entry.
Suspended - No Start Conditions: Eithertherearenostartconditions,orallthestartconditions
aredisabled.Addastartcondition,orenableastartconditionthatisalreadypresenttoleavethis
suspendedstate.
Suspended - No Stop Conditions: Eithertherearenostopconditions,orallthestopconditions
aredisabled.Addastopcondition,orenableastopconditionthatisalreadypresenttoleavethis
suspendedstate.
Suspended - Start Equation Error: Giventheenabledstartconditions,TheStart Equation could
notbeevaluated.The Call to Start hasfurtherdetailsregardingthereasonforthiserror.Ifthe
Call to Start shows"Error:UnrecognizedSymbol"or"Error:EquationdidnotParse"thenastart
conditionneedstoberenamed.Thenamecannotcontainspacesorspecialsymbols(exceptan
underscore).IftheCall to Start shows"Error:VariableNotMapped",itmeansthatthe Value to
Test ofoneofthestartconditionswasremovedfromthecontroller.Theusershouldremovethat
startconditionandadditagainafterensuringtheValue to Test existsonthecontrolleronceagain.
Suspended - Stop Equation Error: Giventheenabledstopconditions,TheStop Equation could
notbeevaluated.The Call to Stop hasfurtherdetailsregardingthereasonforthiserror.Ifthe
Call to Stop shows"Error:UnrecognizedSymbol"or"Error:EquationdidnotParse"thenastop
conditionneedstoberenamed.Thenamecannotcontainspacesorspecialsymbols(exceptan
underscore).IftheCall to Stop shows"Error:VariableNotMapped",itmeansthatthe Value to
Test ofoneofthestopconditionswasremovedfromthecontroller.Theusershouldremovethat
stopconditionandadditagainafterensuringtheValue to Test existsonthecontrolleronceagain.
14.7. Alarms
ThegeneratoralarmsareavailableintheStatus & Config page.Thefollowingalarmsareavailableto
alerttheuserofadversesituations:
Generator Startup Frequency High: ThisalarmwillactivatewhentheStartups in Time Period
exceedsitsconfiguredthresholdduringthegivenStatistics Time Period.Thisalarmcould
activatefromawidevarietyofadversesituations,suchaslowbatteryhealth,wherethebattery
chargecyclebecomesshorterasitshealthdegrades.
Page 152 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish