Cordex®CXCHPControllerSoftwareManual|14-Generator
Notice: The Manual Generator Stop button can be pressed When the Generator State is
Running and waiting for generator to run for minimum runtime or Running and waiting
for Call to Stop to be true. The generator is already stopped when the Generator State shows
disabled or suspended.
TheGenerator State showsDisabled iftheGenerator Control issettoDisabled. Themapped
Generator Control Relay willnotbeenergizedinthisstate.
TheGenerator State canalsoshowsuspendedduetoaconfigurationerror.Thefollowingareall
possiblesuspendedstatesalongwithrecommendationstogetoutofthesuspendedstate:
•
Suspended - No Relay Mapped: SelectarelaywhichcontrolsthegeneratorintheGenerator
Control Relay entry.
•
Suspended - No Start Conditions: Eithertherearenostartconditions,orallthestartconditions
aredisabled.Addastartcondition,orenableastartconditionthatisalreadypresenttoleavethis
suspendedstate.
• Suspended - No Stop Conditions: Eithertherearenostopconditions,orallthestopconditions
aredisabled.Addastopcondition,orenableastopconditionthatisalreadypresenttoleavethis
suspendedstate.
•
Suspended - Start Equation Error: Giventheenabledstartconditions,TheStart Equation could
notbeevaluated.The Call to Start hasfurtherdetailsregardingthereasonforthiserror.Ifthe
Call to Start shows"Error:UnrecognizedSymbol"or"Error:EquationdidnotParse"thenastart
conditionneedstoberenamed.Thenamecannotcontainspacesorspecialsymbols(exceptan
underscore).IftheCall to Start shows"Error:VariableNotMapped",itmeansthatthe Value to
Test ofoneofthestartconditionswasremovedfromthecontroller.Theusershouldremovethat
startconditionandadditagainafterensuringtheValue to Test existsonthecontrolleronceagain.
•
Suspended - Stop Equation Error: Giventheenabledstopconditions,TheStop Equation could
notbeevaluated.The Call to Stop hasfurtherdetailsregardingthereasonforthiserror.Ifthe
Call to Stop shows"Error:UnrecognizedSymbol"or"Error:EquationdidnotParse"thenastop
conditionneedstoberenamed.Thenamecannotcontainspacesorspecialsymbols(exceptan
underscore).IftheCall to Stop shows"Error:VariableNotMapped",itmeansthatthe Value to
Test ofoneofthestopconditionswasremovedfromthecontroller.Theusershouldremovethat
stopconditionandadditagainafterensuringtheValue to Test existsonthecontrolleronceagain.
14.7. Alarms
ThegeneratoralarmsareavailableintheStatus & Config page.Thefollowingalarmsareavailableto
alerttheuserofadversesituations:
•
Generator Startup Frequency High: ThisalarmwillactivatewhentheStartups in Time Period
exceedsitsconfiguredthresholdduringthegivenStatistics Time Period.Thisalarmcould
activatefromawidevarietyofadversesituations,suchaslowbatteryhealth,wherethebattery
chargecyclebecomesshorterasitshealthdegrades.