Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
5.3.5.1. Rectifier configuration guidelines
Thefollowingareguidelinesforsettingrectifierconfiguration.Someorallmayapply.
Over Voltage Protection
Threshold
Setthisvalueasfaraboveequalizevoltageorboostvoltageasneeded.Fora48V
system,theusualvalueis60V.Theactualupperlimitofthissettingdependsonthe
rectifiermodel.IftheRectifierConfigurationErroralarmisactive,itusuallymeansthe
OVPthresholdistoohighortooclosetotheequalize,boostorfloatvoltagesetting.It
isnecessarytohaveatleast1V(for48Vsystem)differencebetweenfloat,equalize
andOVPsettings.
System Start Delay SetthisvaluetodelaythestartupofallrectifierswhenACreturnstogiveotherAC
equipmentonsiteachancetostartupfirst.
Module Start Delay Setthisvaluetoapplyastaggeredstartdelaytoindividualrectifiers.Thishelpslim
itACinrushcurrentandgivesthecontrollertimetoengagechargecurrentcontrol,if
enabled,topreventabatterybreakerorfusefromopening.Eachrectifierisassigned
amodulestartdelaythatisamultipleoftheconfigurationvalue.Ifthevalueexceeds
250s,thevaluestartsagainatthelowestmultiple.Forexample,ifthemodulestartde
layis60sandthereareeightrectifiersinthesystem,thestartdelaysassignedtothe
rectifierswillbe:1s,60s,120s,180s,240s,1s,60s,120s.Thismeansthatthreerecti
fierswillbeassignedthesame1s,60s,and120sdelays.
Current Limit/Power Limit Setoneofthesevalues(notboth)tolimittheoutputcurrentoftherectifier.Thisisnor
mallyonlydoneifthesitehasundersizedACbreakersorisrunningonanundersized
ACgenerator.Thesevaluesmustonlybesetwhileinfloatmode.Settingthemwhen
thebatteryisbulkchargingmayresultintoomuchcurrenttothebattery.
Fast Soft Start Setthistoenabledifthesystemhasnobatteriesandtheloaddoesnotturnonwhen
ACreturns.
CL/PL alert Thisisusuallydisabledwhenthesystemhasbatteriestoavoidacurrentlimitorpow
erlimitalarmduringbatterycharging.
Ramp Test Thisisnormallyenabledtodetectifarectifierhasbeendisconnectedfromtheload.
Whenenabledandiftherectifierissourcinglessthan2.5percentofit’smaximum
current,therectifierwillbrieflyraiseit’soutputvoltageby0.5V(fora48Vsystem)
onceperminute.Iftherectifiercannotsourceatleast2.5percentofit’smaximumcur
rent,theramptestwillfailandaRectifierFailalarmwillactivate.
5.3.6. Configure the shunts
Bydefaultthesystemhasoneshunt.Youmayaddorremoveshuntsasneeded.
ToconfigureashuntyouneedanADIOmodulewithcurrentinputs.Theshuntwillmapthecurrentinputs
fromtheADIOmoduletotheLoad Current Source fieldoftheLoadConfigurationtableortheBattery
Current Source fieldoftheBattery Configuration table.
To configure a shunt:
0350058-J0 Rev AL Page 83

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish