Cordex®CXCHPControllerSoftwareManual|14-Generator
1. GotoController > Programmability > Custom Data.
2. SelecttheAdd Delay Timer buttonintheTimers table.
3. SelecttheGO TO buttoninthenewlineitemtoedittheconfiguration.
4. SettheName ofthetimertoExercise Generator.
5. SettheDelay fortheamountoftimethegeneratorshouldrunforwhenitisexercised.
6. Nootherentriesneedtobeconfiguredinthedelaytimer.
7. GotoController > Programmability > Scheduler.
8. SelecttheCreate Scheduled Action buttontolaunchthewizardtocreatethescheduledtimes
whenthegeneratorshouldstartup.FollowthewizardthroughtotheActionpage.OntheAction
page,selecttheExercise Generator (Delay Timer): Force Timer to Start option.
9. Reviewandcompletethewizard.Now,wheneverthescheduledactionruns,the Exercise
Generator timerwillbegincountingdown,andtheOutput willbeTrue duringthistime.
10. ReturntotheGenerator Control page,andlaunchtheAdd Start Condition wizard.
11. NamethestartconditionExerciseGeneratorStart withnospaces,andselectNext.
12. FromtheValue to Test dropdownmenu,findtheExercise Generator delaytimerinthelist,and
selecttheOutput.SelectNext.
13. FromtheTrue If dropdownmenu,selectTrue toindicatethatthestartconditionshouldbetrue
whentheExerciseGeneratorOutput isTrue.
14. Reviewandcompletethewizard.
15. Next,launchtheAdd Stop Condition wizard.
16. NamethestopconditionExerciseGeneratorStop withnospaces,andselectNext.
17. FromtheValue to Test dropdownmenu,again,findtheExerciseGeneratordelaytimerinthelist,
andselecttheOutput.SelectNext.
18. FromtheTrue If dropdownmenu,thistimeselectFalse toindicatethatthestopconditionshould
betruewhentheExerciseGeneratorOutput isFalse.
19.
Reviewandcompletethewizard.
Notice: The generator control now has a start condition and a stop condition that will
become true or false according to the schedule you created. To ensure correct generator
on/off control, ensure that other start and stop conditions do not interfere with this schedule
by using the test buttons on the start and stop conditions.
14.5. Start and stop logic
Inadditiontotheautomaticon/offcontrol,thegeneratorcanbestartedandstoppedmanuallywiththe
Manual Generator Start andManual Generator Stop buttons.Thegeneratorcannotbemanually
startedorstoppedwhentheGenerator State showsdisabledorsuspended.SeeGeneratorstate (on
page 151) formoredetails.
TheEquation Stability Delay setsthetimethatthe Start or Stop Equations mustholdtheirnewvalue
beforetheCall to Start orCall to Stop changes.