Cordex®CXCHPControllerSoftwareManual|23-Troubleshooting
Turn On Inverters
Configuration Helper
23.3.4. Troubleshoot and clear the system error alarm
OccasionallytheinvertersystemwillactivateaSystem Error alarm.Thismayhappenaftermomentary
ACoutages,breakertrips,falsecommunicationproblems,orotherunusualevents.TheSystem Error
alarmisaremindertochecktheT2Slogfile.Itisrecommendedtodownloadandviewthelogfileforany
possibleproblems.Downloadingthelogfilewillalsoclearthealarm.
To check the T2S log file:
1. DeterminewhichT2Sisthesourceofthealarm.NavigatetoSystems > Inverter System > Live
Alerts andlookfortheCheck Log File alarminthelist.WhenevertheCheck Log File alertis
active,theSystem Error alarmwillalsobeactive.TheCheck Log File alertwillbeshownwiththe
serialnumberoftheT2Sthatiscausingthealert.
2. GotoSystems > Inverter System > Inventory > T2Ss andselecttheGO TO buttonoftheT2S
identifiedinthepreviousstep.
3. IntheT2S Expert Operations table,selectGet Log File from T2S.Thiswillinitiateatransferof
thelogfilefromtheT2S.
4. Oncethelogfilehasbeenreceived,selectDownload tosavethefiletoyourcomputer.
5.
Openthefileandlookforanyevententriesthatmightindicateapersistentissue.Forexample,
modulefailuresorcommunicationproblems.Theseproblemsmayindicatetheneedtoreplacea
moduleorinspectcommunicationwiring.
OncethelogfilehasbeentransferredfromtheT2S,theSystem Error alarmwillclear.
23.3.5. Phase saturation alarm
ThePhase Saturation alarmindicatesthatoneormorephasesaredrawingtoomuchpower.Thealarm
activateswhentheratioofactualoutputpower,overthetotalinstalledpower(excludingredundant
inverters),exceedstheSaturation Alarm Threshold parameterconfiguredontheT2Scontroller.This
valueisnormallysetto100percent.ToverifythethresholdvaluedownloadtheT2Sconfiguration.
To check the T2S Saturation Threshold:
1. GotoSystems > Inverter System > Inventory > T2Ss andselecttheGO TO buttonoftheT2S
identifiedinthepreviousstep.
2. IntheT2S Expert Operations table,selectGet Configuration File from T2S.Thiswillinitiatea
transferoftheconfigurationfilefromtheT2S.
3. Oncethefilehasbeenreceived,selectDownload tosavethefiletoyourcomputer.
4. Openthefileinatexteditorandsearchfor“Saturationalarmthreshold”.Thesearchshouldfinda
linesimilarto:“;556;;Saturationalarmthreshold;;80;;%;“.Thevalue80indicatesthethresholdis
80percent.
Page 264 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish