Cordex®CXCHPControllerSoftwareManual|7-Invertersystems
Figure 7-3 AfullyconfiguredXMBSbypassswitchwithhardwiredI/Osignals
Figure 7-4 AfullyconfiguredXMBSbypassswitchwithCANsignals
7.8. Configure the breaker or fuse
Theinvertersystemcanhaveoneormorebreakersandfuses.Analarmconditionoccurswhenabreaker
orfuseisopen.Whenfirstcreatinganinvertersystem,twobreakersandafusearecreatedbydefault.
Theyshouldberemovedifnotneeded.
To configure a breaker or fuse:
1. GotoSystems > Inverter System > Inventory > Breakers, Fuses and Bypass Switches.Select
theAdd Breaker or Fuse buttonifneeded.Ifabreakerorfuseswitchexists,butneedstobe
removed,intheBreakers and Fuses table,selectRemove.
2. SelecttheGO TO buttonofthebreakerorfusetoconfigure.
3. IntheConfiguration table,entertheName,Description andInput Source values.Whenthe
valueoftheinputsourceisActive,thebreakerorfuseisopen.Alternatively,selecttheConfigure
Breaker or Fuse wizardtobepromptedfortheessentialconfigurationrequiredforthebreakeror
fusetofunction.
4. IntheAlarms table,selecttheGO TO buttonoftheBreaker/Fuse Open alarmandconfigureas
required.