5.3.8. Configure the current transducer
Thesystem,bydefaultdoesnotcontainanycurrenttransducers.Youcanaddorremovecurrent
transducersasneeded.ToconfigureacurrenttransduceryouneedavoltageinputonanADIOmodule.
ToconfigureacurrenttransducerwithanCordex®CXCHPCT-IPMmodule,youneedashuntinputon
anADIOmodule.
To configure a current transducer:
1.
Gotothesystemwhereyouwanttoaddthetransducerandnavigatetotheinventorypage.Goto
Systems > DC System > Inventory > Other Transducers.IntheOther Transducers table,there
willbealistofcurrenttransducersinthesystem.Addorremovethemfromthispage.
YoumaybeusingacurrenttransducerwithInterface & Power Module (IPM).Thisdevicetakes
thevoltagereadingfromacurrenttransduceranddividesthereadingby50.Thefactoredvoltage
readingisthensenttotheCordex®CXCHPL-ADIOperipheralshuntinput.
2. SelecttheGO TO buttonfortheCurrent Transducer youwishtoconfigure.
3. IntheConfiguration table,selectConfigure Current Transducer tolaunchthewizardand
completeeachsteptoconfigurethetransducer.
4. EntertheMeasurement Range inamps.
5. EntertheRange in Volts.
6. SelectCT Current Source.Thiscanbeanyvoltagesource.
7. Optional:entertheOffset calibrationfortheCurrent Transducer ifthereadingerroristoolowor
high.
5.3.9. Configure the general purpose transducer
Thesystem,bydefaultdoesnotcontainanygeneralpurposetransducers.Youcanaddorremove
generalpurposetransducersasneeded.Toconfigureageneralpurposetransduceryouneedavoltage
inputonanADIOmodule.
To configure a general purpose transducer:
1. Gotothesystemwhereyouwanttoaddthetransducerandnavigatetotheinventorypage.Goto
Systems > DC System > Inventory > Other Transducers.IntheGeneral Purpose Transducers
table,therewillbealistofgeneralpurposetransducersinthesystem.Addorremovethemfrom
thispage.
2. SelecttheGO TO buttonfortheGeneral Purpose Transducer youwanttoconfigure.
3. IntheConfiguration tableassignanameandadescription.
4. SelectTransducer Input Source.Thiscanbeanyvoltagesourceoracustomdata.
5. EntertheTransducer Input Minimum in Volts andTransducer Input Maximum in Volts.
6. EntertheTransducer Output Minimum andTransducer Output Maximum.
7. SelectUnits and Precision.
8. Optional:EntertheOffset calibrationforthecalculatedValue ifthereadingerroristoolowor
high.
0350058-J0 Rev AL Page 85