Cordex®CXCHPControllerSoftwareManual|7-Invertersystems
7.5. Configure the T2S inverter controller
TheconfigurationoftheT2Sinvertercontrolleroccursprimarilyduringthecommissioningprocess.There
aretwooptionalsettingsthatanoperatormaywantsetafterthecommissioningiscomplete:theT2S
controllernameanddescription.
Additionally,therearesomeT2Smoduleconfigurationparametersforthenumberofmodulesperphase
andtheamountofinverterredundancyinaphasethataresetduringtheaddandremovewizards.Thisis
whyitisrequiredtousethesewizardswhenchangingthenumberofinvertersinasystem.
To configure a T2S inverter controller:
1. GotoSystems > Inverter System > Inventory > T2S andselecttheGO TO buttonoftheT2S
module.
2. IntheConfiguration table,entertheName andDescription.
7.6. Configure the inverters
Theinvertersarenormallyconfiguredautomaticallywhenusingthecommissioningandaddinverters
wizards.Theinverterparametersthatareconfiguredautomaticallyare,ACandDCinputgroup,aswell
asthebayID,shelfID,andslotID.
Toreconfigureaninverter,removetheinverterfirst,usinguseRemove Inverters wizard.Additbackinto
thesystemusingtheAdd Inverters wizard.Thisensuresthatthesystemconfigurationremainscorrect
andconsistent.
Alternatively,thenumberofredundantinvertersperphasecanbechangedusingtheConfigure Inverter
Redundancy wizard.ToaccessthewizardgotoSystems > Inverter System > Configure System.
ForexpertusersitispossibletochangetheinvertersDCInputgroupandbayID,shelfID,andslotID.
To configure inverter values manually:
1. GotoSystems > AMPS HP2 Inverter System > Inventory > Inverters > Status andselectthe
GO TO buttonfortheinverter.
2. IntheInverter Mapping table,settheBay ID andShelf ID andSlot ID tothedesiredvalues.
3. LaunchtheChange DC Input Group wizardandfollowthesteps.
7.7. Configure the bypass switch
Theinvertersystemcanhaveoneormorebypassswitches.Thebypassswitchwillraiseanalarmwhen
theinvertersystemgoesintobypassmode.
Ifthereismorethanonebypassswitch,thentheinvertersystemwillgointobypassmodewhenany
ofthebypassswitchesareactivated.Duringcreationoftheinvertersystemadefaultbypassswitch
iscreated.Ifaphysicalbypassswitchdoesnotexist,thebypassswitchshouldberemovedfromthe
system.
Page 110 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish