Cordex®CXCHPControllerSoftwareManual|7-Invertersystems
7.5. Configure the T2S inverter controller
TheconfigurationoftheT2Sinvertercontrolleroccursprimarilyduringthecommissioningprocess.There
aretwooptionalsettingsthatanoperatormaywantsetafterthecommissioningiscomplete:theT2S
controllernameanddescription.
Additionally,therearesomeT2Smoduleconfigurationparametersforthenumberofmodulesperphase
andtheamountofinverterredundancyinaphasethataresetduringtheaddandremovewizards.Thisis
whyitisrequiredtousethesewizardswhenchangingthenumberofinvertersinasystem.
To configure a T2S inverter controller:
1. GotoSystems > Inverter System > Inventory > T2S andselecttheGO TO buttonoftheT2S
module.
2. IntheConfiguration table,entertheName andDescription.
7.6. Configure the inverters
Theinvertersarenormallyconfiguredautomaticallywhenusingthecommissioningandaddinverters
wizards.Theinverterparametersthatareconfiguredautomaticallyare,ACandDCinputgroup,aswell
asthebayID,shelfID,andslotID.
Toreconfigureaninverter,removetheinverterfirst,usinguseRemove Inverters wizard.Additbackinto
thesystemusingtheAdd Inverters wizard.Thisensuresthatthesystemconfigurationremainscorrect
andconsistent.
Alternatively,thenumberofredundantinvertersperphasecanbechangedusingtheConfigure Inverter
Redundancy wizard.ToaccessthewizardgotoSystems > Inverter System > Configure System.
ForexpertusersitispossibletochangetheinvertersDCInputgroupandbayID,shelfID,andslotID.
To configure inverter values manually:
1. GotoSystems > AMPS HP2 Inverter System > Inventory > Inverters > Status andselectthe
GO TO buttonfortheinverter.
2. IntheInverter Mapping table,settheBay ID andShelf ID andSlot ID tothedesiredvalues.
3. LaunchtheChange DC Input Group wizardandfollowthesteps.
7.7. Configure the bypass switch
Theinvertersystemcanhaveoneormorebypassswitches.Thebypassswitchwillraiseanalarmwhen
theinvertersystemgoesintobypassmode.
Ifthereismorethanonebypassswitch,thentheinvertersystemwillgointobypassmodewhenany
ofthebypassswitchesareactivated.Duringcreationoftheinvertersystemadefaultbypassswitch
iscreated.Ifaphysicalbypassswitchdoesnotexist,thebypassswitchshouldberemovedfromthe
system.
Page 110 0350058-J0 Rev AL