Cordex®CXCHPControllerSoftwareManual|23-Troubleshooting
Table 23-1 Troubleshootingpowersave(continued)
Issue Possible cause Solution
ules Failed, In Fold
back or Unsupport
ed
hightemperature,or
lowACinputvoltage.
Waitfortemperaturetodrop.
Foruniversalinputrectifiersoperatingat120Vacnominalinputvolt
age,powersavecannotbeusedandshouldbedisabled.These
unitstypicallycanonlybeloadedtoaround50percent,duetolow
inputvoltagederatingsopowersavehasnobeneficialeffect.
PowerSavestatus
is:Stopped - Total
Load Current In
valid
Incorrectconfigura
tionofloadcurrent;
lostcommunication
withrectifiers.
Checkconfigurationofloadsandshunts.
Restorerectifiercommunication.
PowerSavestatusis:
Suspended
ACfailorbatterytest. RestoreAC.
Waitforbatterytesttocomplete.
PowerSavestatusis:
Stopped - System
Voltage Invalid
ADIOcommunication
lostorincorrectsys
temvoltageconfigu
ration.
CheckADIOcommunicationandrestore.
Checksystemvoltageconfiguration.
PowerSavestatus
is:Stopped - Bat
tery Charge Current
Limit Invalid
Batterychargelimit
notconfigured.
Configurebatterychargecurrentlimit.
PowerSavestatus
is:Stopped - Invalid
Data
Dataessentialto
powersavecannot
becomputed.
Checkalloftheaformentioneditems.
Notenoughmodules
areonorbatteryis
discharging
Module Power For
Maximum Efficien
cy settingisabove
themaximumpossi
blepowerachievable.
CheckthevaluesforcurrentandpowercapacityunderSystems >
DC System > Inventory > Rectifiers > Configuration.Theseval
ueslimitthemaximumoutputpowerachievablebytherectifierand
shouldbesetto100percent.
23.3. Troubleshoot an inverter system
Incorrect system configuration
Ifthesystemhasbeenincorrectlyconfiguredwiththewrongnumberofphases,thecommissioning
wizardwillneedtobeexecutedagain.
Page 262 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish