Cordex®CXCHPControllerSoftwareManual|19-Maintainingthesystem
1. GotoSystems > Inverter System > Inventory > Inverters > Status.Thisviewshowsall
inverterswithinthesysteminatableview.Onecolumnwithinthetabledisplaysthenumberof
activealerts.FindaninverterwithanalertandselecttheLocate button.ThiswillcausetheLEDs
onthefrontpaneloftheinvertertoflashfortwoseconds.
2. YoucanalsoselecttheGO TO buttonoftheinverter.ThisviewshowsthebayID,shelfID,and
slotIDoftheinverterintheInverter Mapping table.Normallythisinformationispopulatedduring
systemcommissioning,butitcanalsobechangedhereincaseitisincorrectorwasnotinitially
set.
Notice: If these values have been set, use them to physically locate the inverter. If the
values have not been set or appear to be incorrect, you can use the Locate button to find
the inverter and set the bay ID, shelf ID, and slot ID as required.
19.2.5. Alarms and alerts
TheinvertersystemhasasetofalarmsthataregeneratedbythealertsontheT2Ssystemandinverters.
ThesystemalarmsareshownintheActive Alarms table.
Toseealltheactivealertswithinthesystem,gotoSystems > Inverter System > Live Alerts.Thislive
informationcomesfromtheT2Ssystem,andisthesourceofinvertersystemalarms.
Whentheinvertersystemhasanactivealarm,gototheLive Alerts table.Theinformationinthistable
indicateswhichT2Ssystemorinvertertoinvestigatetofindthecauseofthealarm.
19.2.6. Replace a T2S inverter system
IfaT2Ssystemfailsandneedstoreplaced,removetheoldT2SsystemandpluginthenewT2Ssystem.
GotoModules > All Modules andusetheReplaceT2Swizardtopartiallytransferconfigurationfromthe
oldT2SsystemtothenewT2Ssystem.Itmaybenecessarytowaitforupto20minutesasthenewT2S
systemcontinuestobeconfiguredbycommunicatingwiththeinverters.
Ifsystemisnotoperatingproperlyafterwaiting,thenthesystemneedstoberecommissionedfortheT2S
systemtobeconfiguredcorrectly.Followtheseinstructions:
1. UnplugthefailedT2Ssystem.
2. GotoSystems > Inverter System > Inventory > T2Ss andselectForget All in Comms Lost.
TheT2Ssystemwilldisappearfromthetable.
3. InsertthenewT2Ssystem,andthenwaitforittodisplayintheModules Available for
Assignment table.ItwilltakeseveralminutesforthecontrollertoacquirethenewT2Ssystem.
Ingeneralitisassignedtothesystemautomatically,anddisplaysintheT2Ss table.Ifitdoesnot
occur,usetheAssign All buttontodothismanually.
4. PutthesysteminBypasstokeeptheloadpoweredduringthecommissioningprocess.
5. GotoSystems > Inverter System > Configure System andselecttheCommission Inverter
System wizardintheConfiguration table.