Cordex®CXCHPControllerSoftwareManual|19-Maintainingthesystem
6. Followthewizardinstructionstorecommissionthesystem.
7. Whencompleted,selecttheAdd Inverters buttontolaunchtheaddinverterswizardandaddall
theinverterstothesystem.YoucanalsolaunchthiswizardfromSystems > Inverter System >
Inventory > Inverters > Status.
TheT2Ssystemhasbeenreplaced,andtheinvertersystemhasnoactivealarms.
19.2.7. Shelf layout
Shelflayoutisonlyavailableviathewebinterface.
WhentheinvertershavebeenconfiguredwithbayID,shelfID,andslotID,theShelf Layout page
displaysaphysicalviewoftheinverters,thealertstatusandtheoutputpowerofeachinverter.Thetext
thatshowstheoutputpowerisalinkthatopensanewpagetodisplaytheinverterdetails.
ForinvertersystemsthatusefourT2SandTUSmodules;TUSmoduleswilldisplayintheShelf Layout
page,butbecausetheydonothavebayID,shelfID,orslotIDtheyareonlydisplayedinthetable.
19.3. Line power system maintenance
Thissectioncoverslinepowersystemmaintenanceincluding:replacinglinepowermodules,andturning
offpowertotheloads.
19.3.1. Power off and on line power loads
Alinepowerloadusuallyhasmultiplechannelsfromdifferentlinepowermodulesassignedtoit.Itmay
benecessarytooccasionallypoweroffthenpowerontheload.
To power off or on a load:
1. GotoSystems > Line Power System > Inventory > Line Power Loads andselecttheGO TO
buttonfortheloadtobepoweredoff.
2. IntheStatus table,verifythattheChannels valueisatleast1.ThePower On/Off buttonswill
onlyworkifthereareoneormorechannelsassignedtotheload.
3. IntheConfiguration table,selectthePower Off button.Afterafewmoments,theChannels
Enabled,Total Output Current andTotal Output Power valuesintheStatus tablewillgoto
zero.Thisindicatesthattheloadhasbeenturnedoff.ThePower Off buttonwillbecomedisabled
andthePower On buttonbecomesenabled.
4. Toturnontheload,selectthePower On button.
19.3.2. Replace line power modules
Ifalinepowermoduleisfoundtohavefaileditcanbeeasilyreplacedwithoutlosinganyconfiguration.
To replace a module:
0350058-J0 Rev AL Page 171

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish