Cordex®CXCHPControllerSoftwareManual|19-Maintainingthesystem
6. Followthewizardinstructionstorecommissionthesystem.
7. Whencompleted,selecttheAdd Inverters buttontolaunchtheaddinverterswizardandaddall
theinverterstothesystem.YoucanalsolaunchthiswizardfromSystems > Inverter System >
Inventory > Inverters > Status.
TheT2Ssystemhasbeenreplaced,andtheinvertersystemhasnoactivealarms.
19.2.7. Shelf layout
Shelflayoutisonlyavailableviathewebinterface.
WhentheinvertershavebeenconfiguredwithbayID,shelfID,andslotID,theShelf Layout page
displaysaphysicalviewoftheinverters,thealertstatusandtheoutputpowerofeachinverter.Thetext
thatshowstheoutputpowerisalinkthatopensanewpagetodisplaytheinverterdetails.
ForinvertersystemsthatusefourT2SandTUSmodules;TUSmoduleswilldisplayintheShelf Layout
page,butbecausetheydonothavebayID,shelfID,orslotIDtheyareonlydisplayedinthetable.
19.3. Line power system maintenance
Thissectioncoverslinepowersystemmaintenanceincluding:replacinglinepowermodules,andturning
offpowertotheloads.
19.3.1. Power off and on line power loads
Alinepowerloadusuallyhasmultiplechannelsfromdifferentlinepowermodulesassignedtoit.Itmay
benecessarytooccasionallypoweroffthenpowerontheload.
To power off or on a load:
1. GotoSystems > Line Power System > Inventory > Line Power Loads andselecttheGO TO
buttonfortheloadtobepoweredoff.
2. IntheStatus table,verifythattheChannels valueisatleast1.ThePower On/Off buttonswill
onlyworkifthereareoneormorechannelsassignedtotheload.
3. IntheConfiguration table,selectthePower Off button.Afterafewmoments,theChannels
Enabled,Total Output Current andTotal Output Power valuesintheStatus tablewillgoto
zero.Thisindicatesthattheloadhasbeenturnedoff.ThePower Off buttonwillbecomedisabled
andthePower On buttonbecomesenabled.
4. Toturnontheload,selectthePower On button.
19.3.2. Replace line power modules
Ifalinepowermoduleisfoundtohavefaileditcanbeeasilyreplacedwithoutlosinganyconfiguration.
To replace a module:
0350058-J0 Rev AL Page 171

Table of Contents