Cordex®CXCHPControllerSoftwareManual|22-Usingcustomviews,data,timers,counters,scheduler,andcustomactions
Condition Value: ThepresentvalueofCondition.
Field Value: ThepresentvalueofField To Change.
Change field to constant action operation
TheChange Field To Constant actionoperatesasfollows:
WhentheCondition Value isfalseorunknown,Field To Change willbesettoField Value When
Condition True.
WhentheCondition Value istrue,Field To Change willbesettoField Value When Condition
False Or ---.
22.9.2.1. Configure a change field to constant action
OnewaytouseaChange Field To Constant Action istosetAuto DC Priority.Thefollowingdescribes
howtoconfigureaChange Field Action To Constant tocontroltheamountofpowertheInverter
SystemtakesfromDC,basedonthetimeofday.
GotoSystems > Inverter System > System Functions andintheManual DC Priority table,ensure
thatManual DC Mode isEnabled.
1. GotoController > Programmability > Scheduler.
2. SelecttheCreate Time Span wizardtoselectthedaysandtimes.
3. GotoController > Programmability > Custom Data.
4. SelectAdd Change Field To Constant Action,andselecttheGO TO button.
5. IntheConfiguration table,selectField To Change,selecttheAMPS HP2 system andthen
Desired DC Input Power.
6. IntheConfiguration table,selectCondition > Time Span > Within Time Span.
7.
IntheConfiguration table,selectField Value When Condition True andsetto100%.
ThiscausestheinvertersystemtopullallitspowerfromDCduringthemoreexpensivehoursfor
powerusage.
8.
IntheConfiguration table,selectField Value When Condition False to0%.
ThiscausestheinvertersystemtopullallitspowerfromACduringlessexpensivehoursofpower
usage,allowingthebatteriestochargeduringthattimeperiod.
22.9.3. Configure a change field to variable action
TheChange Field To Variable Action featurecanbeusedtochangethevalueofafieldtothevalueof
aCustom Data. Thiscanbeusefultocontrolthestateofthesystembasedonexternalconditions.For
example,therectifierspoweroutputcanbeadjustedbasedonalimittotheamountofACpowerthat
shouldbeconsumed.
ToaccessthisfeaturegotoController > Programmability > Custom Data.
0350058-J0 Rev AL Page 253

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish