Cordex®CXCHPControllerSoftwareManual|22-Usingcustomviews,data,timers,counters,scheduler,andcustomactions
AChange Field To Variable actionhasfiveconfigurationfields:
Name: Theeditablenameofthisitem.
Description: Additionalinformationtodescribethisitem.
Field To Change: ThefieldthatwillhaveitsvaluechangedtothevalueoftheconfiguredCustom
Data.
Set Field To Custom Data: ThevalueofField To Change willbesettothevalueofthisCustom
Data.
Field Value Change Interval: ThenumberofsecondsbetweeneachtimethevalueofField To
Change willbesettothevalueofSet Field To Custom Data.
Therearealsofieldsthatdescribethestateoftheaction:
Last Error Condition: Describesifthereareanyerrors,eitherwiththeconfigurationorthe
operationofthisaction.
Field Value: ThepresentvalueofField To Change.
Field Range: TherangeforField To Change.ThevalueofField To Change willonlybesetifthe
valueoftheconfiguredCustom Data iswithinthisrange.
Custom Data Value: ThepresentvalueofSet Field To Custom Data.
Time To Next Possible Change: TheamountofsecondsuntilthenexttimeField To Change will
haveitsvaluesettothevalueoftheconfiguredCustom Data,ifthevalueisdifferentandwithin
range.
Change field to variable action operation
TheChange Field To Variable actionoperatesasfollows:
ThevalueofField To Change willbesettothevalueoftheCustom Data thatSet Field To
Custom Data isconfiguredtouse.
ThisvaluewillbesetonanintervalbasedonthevalueofField Value Change Interval.For
example,ifthisfieldissetto300seconds(thedefault),thevalueofField To Change willbeset
every300seconds.
Field To Change willonlybesetifthevalueoftheconfiguredCustom Data isdifferentthanthe
presentvalueofField To Change,andiswithinrangeforthisfield.
Page 254 0350058-J0 Rev AL