Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
To restart the controller from the web interface:
1. FromthemaindashboardgotoController > About > General.
2. SelecttheRestart Controller button.
3. SelectRestart whenprompted.
4. TheController Restart windowdisplaysprogressviaaprogressbar.
5. Thecontrollerscreengoesblack,andtheLEDscyclewhilerestartisinprogress.
Oncecomplete,theloginpagedisplaysonthewebinterface,andtheCordex®HPlogodisplaysonthe
controller.
20.3.2. Restart the controller via the LCD
Notice: Ensure that the controller software or operating system software is not being updated.
TorestartthecontrollerviatheLCD:
1. Fromthemaindashboardofthecontroller,selectShortcuts,thenselectRestart.
2. SelecttheExecute buttontoconfirm.
Thefrontscreenblacksout,andtheLEDstatuslightscycleuntiltherestartiscomplete.Oncetherestart
completes,theCordex®HPlogodisplays.
20.3.3. Powering down the controller
Sometimesitmaybenecessarytopowerdownthecontrollertoreplace,remove,orrepairrectifiers.
Notice: You must use the LCD or web interface to reset the controller. This ensures that recent
changes and files are saved properly.
1. Fromthemaindashboardonthewebinterface,gotoController > About > General andthen
selectcontrollerreset.
-or-
2. FromthemaindashboardontheLCD,selectShortcuts,thenselectReset.
3. SelectExecute toconfirm.
4.
WhilethecontrollerLEDsareperformingachasepattern,powerdownthecontrollerbyremoving
thepowerpinontheright-sideofthecontroller.
Afterareset,thecontrollerLEDswillperformachasepatternthatindicatesthatthecontrolleris
booting.Itissafetoremovepowerwhilethecontrollerisbooting.Oncethatchasepatternstops,
thebootsequenceisoveranditisnolongersafetoremovepower.
0350058-J0 Rev AL Page 185

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish