Cordex®CXCHPControllerSoftwareManual|5-DCpowersystems
Estimated State of Charge (SOC),andanEstimated Battery Runtime (RTR)remainingatalltimes.
Itisnotalwayspracticaltoestimatethesevalues.Forexample,ifthesystemgoesintoachargingstage
immediatelyafterarestart,thereisnowaytoestimatetheSOCorRTR.
Theaccuracyoftheestimatedbatteryhealthimprovesasthebatteryundergoesmoredischargecycles
anditalsoimproveswithdeeperdischarges.
IfabatterydischargeoccursthatgoesbelowanSOCvalueof80percent,thentheBattery Runtime
& Health Estimation functioncreatesaLast Battery Discharge Summary,aLast Battery Recharge
Summary andrecalculatestheEstimated Battery Health.Ifestimatedbatteryhealthislessthan80
percentthenthatbatteryisnormallyduetobereplaced.
5.2.6. Low voltage disconnect operation
WheneverthesystemparametersrequirestheLVDtobeactivated,a60secondcountdownandaudible
warningbegins.Whenthecountdownreacheszero,theLVDisactivated.
Duringthecountdown,acommandinthedisconnectmenucanbepressedtoinhibitLVDactivation.
WhenthedisconnectfirstchangestoPending,everyuserloggedintothesystemwillreceivenotification
thatthedisconnectisabouttoactivate,andtheoptiontoinhibitit.Toreleasetheinhibit,youmustactivate
thereleasecommandforeachLVD.
Therearethreetypesofdisconnects:“legacy”disconnect,generalpurposedisconnect,andbattery
disconnectwithlatchingcontactor.
Legacy disconnect
Thelegacydisconnectisthefirstdisconnectavailableonthecontroller.Itofferstheabilitytodisconnect
basedonvoltage,timeelapsedsinceACfail,andthestateofchargeofthebattery.
General purpose disconnect
Thegeneralpurposedisconnectisbestsuitedforuseasaloadsheddingdisconnect.Itcanbeconfigured
todisconnectbasedonvoltage,oruptothreecustomizabledisconnectconditions.Therearethree
customizablereconnectconditionsinadditiontotheusualvoltagereconnectthreshold.
Whenusingtheoptionaldisconnect,notethefollowingconditions:
Thevoltagemustbelessthanthedisconnectthresholdor
Oneormoreoptionaldisconnectconditionsaretrueand
Alloptionalreconnectsmustbeunknownorfalse
Iftheoptiontodisallowdisconnectduringbatterytestistrueandbatterytestisactive,the
disconnectwillnotactivateuntilbatterytestisnolongeractiveorthisoptionisdisabled.
Whenusingtheoptionalreconnect,notethefollowingconditions:
Page 72 0350058-J0 Rev AL

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish