Cordex®CXCHPControllerSoftwareManual|2-Softwarereleasehistory
PerformancelogsandDatalogscannotrunifthereisaClock Error Alarm.Onceyoucorrectthe
clockerroralarm,itisagoodideatorestartthecontrollertoensurethatalloftheloggingstartsup
properly.
TheDataloghasaCapture When True configurationfieldthatisusedtocontrolwhendatais
captured.IfyoudeletethevaluethatCapture When True ispointingto(forexample,aCustom
Data value),theCapture When True fieldshouldchangetoUnknownbutdoesnotuse.Theuser
hastomanuallysetthisfieldbacktoUnknownortheDatalogwillcontinuetousetheoldvalue.
CustomdatawillsometimesgiveanerrormessageVariable Not Mapped whentherealerror
messageshouldbeVariable Has a Value of Unknown.
DigitalinputstatefordigitalinputsonBDFBdeviceswascorrected.Ifaversion3.22orearlier
configurationfileisuploaded,thefollowingconfigurationfieldsmaynotbeimportedasexpected.
Checkthefollowingforcorrectness:BDFBdigitalinputActive When field;thecustomdata
variableusingaBDFBdigitalinput;andtheuseralarmusingaBDFBdigitalinput.
IftheDisconnectActivealarmisactive,andtherelayisunmappedfromthedisconnect,thealarm
willnotclear.Toclearthealarm,remaparelayandclearthealarmcondition,orremovethe
disconnectfromthesystem.
Thein-shelfcontrollerdisplaydoesnotdisplayauxiliarysystems.Whenoneofthesesystemsis
selectedfordisplay,thedisplayshowsthetextNo System.
Duetoperformanceconstraintsonthecontroller,itisrecommendedtocreatenomorethana
totaloffiveSmartBDFBorUser-Defineddistributionsubsystems,or40SmartE2distribution
subsystems.ThisdifferenceinlimitisduetoSmartBDFBandUser-Definedsubsystemsrequiring
moreprocessingpowerthanSmartE2subsystemsduetotheamountofdataprovided.A
combinationofthetwolimitscanalsobecreated(forexample,threeSmartBDFBsubsystems
and16SmartE2subsystems).IfaDCsystemisalsorequired,thentherecommendedlimitisno
morethanthreeSmartBDFBor24SmartE2subsystems.Theserecommendationsassumeno
morethanlight(10datapoints)SNMPpolling.IfmoreSNMPdataisrequireditisrecommendedto
reducethenumberofBDFBorE2systemstocompensate.
Eventsthatoccurveryearlyduringthecontrollerstartupprocessmaybeloggedwithatime-stamp
thatisinUTCtimeratherthanlocaltime.
Alightlyloadedorphaseunbalancedinvertersystemdisplaysinaccuratereadingsforsome
values.Whenasystemisloadedsufficiently,thereadingswillbecorrect.
Inversion6.00andlater,theBatteryTemperatureAnomalyalarmisdisabledbydefaultonthe
Battery.Ifitisrequired,setuponeormorebatterystringstousethisalarm.
WhenusingtheUPS-MIBwiththeFXMHPUPS,thecontrollerwillsendtwoalarmtraps.Oneis
fromtheUPS-MIB,theotherisfromtheALPHA-RESOURCE-MIB.
0350058-J0 Rev AL Page 29

Table of Contents

Other manuals for EnerSys Alpha Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EnerSys Alpha Cordex CXC HP and is the answer not in the manual?

EnerSys Alpha Cordex CXC HP Specifications

General IconGeneral
BrandEnerSys
ModelAlpha Cordex CXC HP
CategoryController
LanguageEnglish