Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
3. Selecttherelaysymbolontherighthandside.Alistofallrelaysisshown.
4. Selectarelaytoandselectthearrowontherighthandside.ATest Relay actionisshownatthe
topofthescreenwiththerelaystatusunderneathit.
5. SelecttheTest Relay actionandselectthearrowontherighthandside.Ifyouarepromptedto
login,selecttheLogin buttonandenterusercredentials.
6. SelecttheExecute buttontostartthetest.Therelaywillchangestateforoneminutebefore
reverting.
7. Tostopthetestortorestartthetest,selectthebackarrow.
Page 222 0350058-J0 Rev AL