Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
• Import andExport ofconfigurationfiles.
•
Upgrade ofthecontrollerapplicationsoftware.
• Upgrade ofthecontrolleroperatingsystemsoftware.
• Import andExport oflicensekeyfiles.
• Upgrade ofmoduleapplicationsoftwareusingACANfiles.
• Downloading ofeventlogsandmodulealerts.
• Export Backup ofthecontrollerapplicationsoftwareandconfiguration.
FileoperationsthatareavailableonlyviatheLCD:
• Restore ofthecontrollerapplicationsoftwareandconfiguration.
Fileoperationsthatareavailableonlyviathewebinterface:
•
Downloading ofperformancelogs,datalogs,andtables.
20.5.2.1. Import and export from the LCD
OntheLCD,gotoMenu > Controller > Files & Upgrades > Configuration & Software Backup >
Configuraton File.TheExport Controller Clone commandallowsyoutoexporttheentirecontroller
configurationtoaconnectedUSBdrive.TheotheroptionsExport System or ADIO andExport
Partial arenotsupportedontheLCD.TheImport commandallowyoutoimportconfigurationfileswith
limitationsasnoted.
Alternatively,gotoShortcuts > Browse USB.Hereyoucanselectaconfigurationfiletoperforman
Import.
Notice: Using the Import command from the LCD has limitations. Importing a configuration file
that is a clone of a controller will always work. However, importing a configuration file that is for
a system, an ADIO module or a partial configuration will only work if the import can be achieved
unambiguously. For example, if the import is intended to change some configuration for an ADIO
module, but there are more than one ADIO module of the same type it will be ambiguous as
to which ADIO module should receive the configuration. Therefore the import will fail. In this
scenario, the web interface should be used to do the import so that the user can choose which
ADIO module should receive the configuration.
20.5.2.2. Application upgrade from the LCD
Therearetwowaystoupgradethecontrollersoftware:
Page 198 0350058-J0 Rev AL