Cordex®CXCHPControllerSoftwareManual|20-Maintainingthecontroller
Import andExport ofconfigurationfiles.
Upgrade ofthecontrollerapplicationsoftware.
Upgrade ofthecontrolleroperatingsystemsoftware.
Import andExport oflicensekeyfiles.
Upgrade ofmoduleapplicationsoftwareusingACANfiles.
Downloading ofeventlogsandmodulealerts.
Export Backup ofthecontrollerapplicationsoftwareandconfiguration.
FileoperationsthatareavailableonlyviatheLCD:
Restore ofthecontrollerapplicationsoftwareandconfiguration.
Fileoperationsthatareavailableonlyviathewebinterface:
Downloading ofperformancelogs,datalogs,andtables.
20.5.2.1. Import and export from the LCD
OntheLCD,gotoMenu > Controller > Files & Upgrades > Configuration & Software Backup >
Configuraton File.TheExport Controller Clone commandallowsyoutoexporttheentirecontroller
configurationtoaconnectedUSBdrive.TheotheroptionsExport System or ADIO andExport
Partial arenotsupportedontheLCD.TheImport commandallowyoutoimportconfigurationfileswith
limitationsasnoted.
Alternatively,gotoShortcuts > Browse USB.Hereyoucanselectaconfigurationfiletoperforman
Import.
Notice: Using the Import command from the LCD has limitations. Importing a configuration file
that is a clone of a controller will always work. However, importing a configuration file that is for
a system, an ADIO module or a partial configuration will only work if the import can be achieved
unambiguously. For example, if the import is intended to change some configuration for an ADIO
module, but there are more than one ADIO module of the same type it will be ambiguous as
to which ADIO module should receive the configuration. Therefore the import will fail. In this
scenario, the web interface should be used to do the import so that the user can choose which
ADIO module should receive the configuration.
20.5.2.2. Application upgrade from the LCD
Therearetwowaystoupgradethecontrollersoftware: