Cordex®CXCHPControllerSoftwareManual|22-Usingcustomviews,data,timers,counters,scheduler,andcustomactions
Onthedetailspageofarowinthetextmappingtable,thereare4entries:
• Name:Thisisthenameofthemappedtext.Itwillappearasthecustomdata'sResult as Text ifit
isthehighestprioritymappedtextthatevaluatestotrue.
• Logic:Thelogicalconditionusedtotestifthistextmappingistrue.IftheLogicissettoEqual-to,
Greater-thanorLess-than,itistestedagainsttheResult as Numeric.IftheLogicissettoIs-True
orIs-False,itistestedagainsttheResult as Boolean.
• Limit:ThevalueusedtotestagainstanEqual-to,Greater-thanorLess-thanlogiccondition.For
equal-tologic,theResult as Numeric mustbewithin+/-0.00001oftheLimittoevaluatetotrue.
TheLimit hasnoeffectforIs-trueorIs-falselogic.Thenumberofdecimalplacesandunitsshown
canbesetusingthecustomdata'sNumeric Units and Precision entry.
• Priority:Thisistheevaluationpriorityofthemappedtext.Thenameofthehighestprioritymapped
textthatevaluatestotrueisassignedtotheResult as Text;priority1ishighest,6islowest.
Thepicturebelowshowsanexampleofhowthetextmappingtablemightbeconfiguredforacustom
datarepresentinganairconditioner'sstate.Inthisexample,theResult as Text willshowas"Off"for
anyResult as Numeric valuelessthan0.5,andwillshowas"Cooling"whentheResult as Numeric is
equalto1.Notethatthereisnomappedtextfornumericvaluesbetween0.5and1;meaningwithinthis
range,theResult as Text willshowasunknown,"---".Alsonote,thatiftwomappedtextsaretrueatthe
sametime,theResult as Text willdisplayonlythemappedtextnamewiththehigherPriority;priority1
ishighest,6islowest.
0350058-J0 Rev AL Page 241