Cordex®CXCHPControllerSoftwareManual|23-Troubleshooting
Table 23-3 TroubleshootingerrorsinalinepowerchannelsCSVfile(continued)
Name Value Analysis of value Solution
InvalidChannelEntry CSVRow#:2;Value:5;LP
Ch:1-1.5
Theerrorwascaughtinthe
CSVfileonrow2.Achan
nelentryvaluewasfound
tobe5for1-1.5which
correspondstotheShelf-
Slot.Channel.
Alinepowermoduleon
lyhasupto4channels.
Changethechannelentry
valuefroma5toavalue
between1to4.
InvalidSlotEntry CSVRow#:3;Value:@;
LPCh:1-@.2
Theerrorwascaughtin
theCSVfileonrow3.A
slotentryvaluewasfound
tobe@for1-@.5which
correspondstotheShelf-
Slot.Channel.
Alinepowershelfcanhave
upto12slots.Thereisan
invalidcharacter(@)for
theslot.Changethevalue
tobebetween1to12.
InvalidShelfEntry CSVRow#:5;Value:1.3;
LPCh:1.3-1.4
Theerrorwascaughtinthe
CSVfileonrow5.Ashelf
entryvaluewasfoundto
be1.3for1.3-1.4which
correspondstotheShelf-
Slot.Channel.
Alinepowersystemcan
haveupto9shelves.The
shelfentrywasadecimal
value.Changetheshelfen
tryvaluetobebetween1to
9.
Page 268 0350058-J0 Rev AL