Upgrade and Maintenance Manual 355
Accessible drives
Ê "Closing the rack door" on page 84
Ê "Enabling BitLocker functionality" on page 107
12.7 Replacing an ODD
12.7.1 Required tools
Preliminary and concluding steps: tool-less
Replacing an ODD:
Phillips PH0 / (+) No. 0 screw driver
12.7.2 Preliminary steps
Perform the following procedures:
Ê Ask the system administrator to eject all remaining backup or optical media
from the backup or optical disk drive before removing it from the server.
Ê "Disabling BitLocker functionality" on page 85
Ê "Opening the rack door" on page 64
Ê "Shutting down the server" on page 65
Ê "Disconnecting power cords" on page 66
Ê "Extending the server out of the rack" on page 69
If further required, remove the server from the rack as described in section
"Removing the server from the rack" on page 70.
Ê "Removing the server cover" on page 72
Ê "Removing the air duct" on page 73
Upgrade and Repair Units (URU)
Average task duration: 10 minutes