RX300 S7
Upgrade and Maintenance Manual 443
Front panel
Ê "Closing the rack door" on page 84
Ê "Enabling BitLocker functionality" on page 107
13.3.3 Replacing the front LAN connector and board
13.3.3.1 Required tools
●
Preliminary and concluding steps: tool-less
●
Replacing the front LAN connector: tool-less
13.3.3.2 Preliminary steps
Perform the following procedures:
Ê "Disabling BitLocker functionality" on page 85
Ê "Opening the rack door" on page 64
Ê "Locating the defective server" on page 56
Ê "Shutting down the server" on page 65
Ê "Disconnecting power cords" on page 66
Ê "Extending the server out of the rack" on page 69
If further required, remove the server from the rack as described in section
"Removing the server from the rack" on page 70.
Ê "Removing the server cover" on page 72
Ê "Removing the air duct" on page 73
Ê "Removing the fan box" on page 183
Field Replaceable Units (FRU)
Average task duration: 15 minutes