Figure 58: Three-Phase Wye AC Power Cord
NOTE: In North America, AC power cords must not exceed 4.5 m
(approximately 14.75 ft) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical
Code (CEC) Section 4-010(3). The cords supplied with the router are in
compliance.
WARNING: The router is pluggable type A equipment installed in a
restricted-access location. It has a separate protective earthing terminal
(sized for UNC 1/4-20 ground lugs) provided on the chassis in addition to the
grounding pin of the power supply cord. This separate protective earthing
terminal must be permanently connected to earth.
CAUTION: Power cords and cables must not block access to device
components or drape where people could trip on them.
Related
Documentation
• Connecting AC Power to a T640 Router with Three-Phase Wye AC Power Supplies on
page 244
• Connecting AC Power to a T640 Router with Three-Phase Delta AC Power Supplies
on page 241
• Replacing a T640 Three-Phase Delta AC Power Supply Cord on page 404
• Replacing a T640 Three-Phase Wye AC Power Supply Cord on page 416
• T640 Three-Phase Delta AC Power Supply Specifications on page 136
• T640 Three-Phase Wye AC Power Supply Specifications on page 136
Copyright © 2017, Juniper Networks, Inc.140
T640 Core Router Hardware Guide