FuelsManager Defense
124 Administrator Manual
Edit Tank Data dialog box - Vessel 2 tab
MAXIMUM FILL This field allows the user to configure the maximum safe
level to which the tank can be filled. FuelsManager uses this
value in the calculation of remaining and available
volume(s). The maximum fill level can be:
User Defined - user can enter any value.
High - Maximum fill level is the same as the high level alarm
limit
High-High - Maximum fill level is the same as the high-high
level alarm limit.
Note! Selecting the 'User Defined' option also enables the Maximum
Operating limit level alarm. This alarm functions independently of the High and
High-High alarms and is intended to give an additional stage of level alarm
monitoring.
MINIMUM
EMPTY
This field allows the user to configure the minimum safe level
to which the tank can be drained. FuelsManager uses this
value in the calculation of remaining and available
volume(s). The minimum empty level can be:
User Defined - User can enter any value.
Low - Minimum empty level is the same as the low level
alarm limit.
Low-Low - Minimum empty level is the same as the low-low
level alarm limit.
Note! Selecting the 'User Defined' option also enables the Minimum
Operating limit level alarm. This alarm functions independently of the Low and
Low- alarms and is intended to give an additional stage of level alarm
monitoring.
GAUGE TYPE This field allows the user to configure the type of automatic
tank gauge used by this tank. FuelsManager uses this
parameter for display only.
MODIFIER This field allows the user to configure the commands
available to the operator for a particular automatic tank
gauge. For example, Raise / Lower.
FLOAT MASS This field allows the user to configure the mass of the float,
FuelsManager uses this to compensate the level value
reported by the tank gauge. Used when LPG volume
calculation method is selected
FLOAT DENSITY This field allows the user to configure the density of the float.
FuelsManager uses this to compensate the level value
reported by the tank gauge. Used when LPG volume
calculation method is selected
FLOAT
DIAMETER
This field allows the user to configure the diameter of the
float. FuelsManager uses this to compensate the level value
reported by the tank gauge. Used when LPG volume
calculation method is selected