Tank configuration data
ADM003GVAE1005 365
Tank configuration data
Tank Configuration Data
DETAIL
This parameter defines which tank detail template is to be displayed for this particular tank. If this value is not
defined, FuelsManager will use the tank detail template defined in the registry key:
HKEY_LOCAL_MACHINE\SOFTWARE\FuelsManager\Detail\Tank
CORRECTION TYPE
These two parameters define the volume correction method to be used in the calculation of Std. Density and Net
Std. Volume. The selection made in the first parameter constrains the available options in the second parameter.
For example, if the user selects API°C, the second parameter is constrained to American Petroleum Institute
tables that are valid for temperatures expressed in °C.
STD TEMPERATURE
This parameter defines the temperature to which the gross volume value will be corrected. The majority of the
correction types define the standard temperature, for these types this field is for display only
K0 - K5
These parameters are only visible when the correction type 'polynomial' is selected, these parameters define the
constants to be used in the polynomial calculation
ALPHA
This parameter is available when an American Petroleum Institute table of type C (table 54C or table 6C) or a
Japan Chemical table is selected. This parameter defines the thermal co-efficient of expansion to be used in the
volume correction method
VCF ROUNDING
This parameter is only available when a Japanese correction type is selected. The rounding options are None,
0.0001, and 0.000001 and are applied to the Volume Correction Factor before all calculations are performed
LEVEL ROUNDING
This parameter is only available when a Japanese correction type is selected. The rounding options are None
and Nearest Integer. Level rounding is applied to the product level before performing each volume calculation
TEMPERATURE ROUNDING
This parameter is only available when a Japanese correction type is selected. The rounding options are None,
0.25, and 0.5. Temperature rounding is applied to the product temperature before performing each volume
calculation
WATER SUBTRACTION
This parameter is only available when a Japanese correction type is selected. The water subtraction options are
None, Gross Volume, and Net Volume. This parameter defines the method of Water Volume compensation.
Water Volume is either; not subtracted; subtracted in the calculation of Gross Volume; or subtracted in the
calculation of Net Volume, respectively