ArchiveManager
ADM003GVAE1005 161
Setting the ArchiveManager schedule
The ArchiveManager writes data on a schedule, based on your entries in the Start
Time and Interval fields in the ArchiveManager Configuration dialog box.
In the following example ArchiveManager, writes the first archive at 10:15 and
then every ten minutes there after.
Start Time – 00:15 / Interval – 10 minutes /
Current Time – 10:08
Archive input and output points
Click on this option to configure ArchiveManager to write input and output points.
Otherwise, the system only writes Tank Points.
Specify archived points
This option lets you specify points to be written from the real-time database to the
ODBC data source. If this option is selected along with the Archive Input and
Output Points option, you can specify both tank and input/output points.
Otherwise, you can only specify tank points.
Step-by-Step
In the Start Time field, enter the number of minutes past the hour that you
want to synchronize the archive data to
In the Interval field, enter the number of minutes you want to leave between
data transfers. The minimum interval is 10 minutes
In the Historical Period field, enter the numbers of days you want from 1
through 9999 days. This is the time period for the archive in days. Any
record older than this time period will be overwritten by newer data
On startup, ArchiveManager takes the start time, the interval, and the
current time, compares these values and determines when the archive
should be updated
If… then…
Archive Input and Output Points and
Specify Archived Points are not
selected
all tanks for every FMDataManager are
archived
Archive Input and Output Points is
selected and Specify Archived Points
is not selected
all tanks and the Input and Output points
for all selected DataManagers are
archived
Archive Input and Output Points is
not selected and Specify Archived
Points is selected
only tank points selected in the Points to
be Archived dialog are archived
Archive Input and Output Points and
Specify Archived Points are selected
every selected tank input point, and tank
output point that has been selected in the
Points to be Archived dialog