This section describes the correction methods and tank calculations used in the
FuelsManager program. Since the volume of the product in a tank varies with the
temperature and density, the user must use a correction method to correct for
variations in temperature and density of the product.
Data rounding
Selecting any of the correction methods designated 'Japan' allows the user to
configure the following special data rounding methods.
Volume Correction Factor (VCF)
•None
• 0.00001
• 0.0000001
Level
This includes both Product and Water Level
•None
• Nearest Integer (i.e. 123.5 millimeters is truncated to 123 millimeters.)
Temperature
This includes Product and Gas Temperature
• None
• 0.25 Degrees
- 0.000 ~0.124 --- 0.00 °C
- 0.125 ~0.374 --- 0.25 °C
- 0.375 ~0.624 --- 0.50 °C
- 0.625 ~0.874 --- 0.75 °C
- 0.875 ~1.124 --- 1.00 °C
• 0.5 Degrees
- 0.00 ~0.29 -- 0.0 °C
- 0.30 ~0.79 -- 0.5 °C
- 0.80 ~1.29 --1.0 °C