FuelsManager Defense
314 Administrator Manual
In addition, FuelsManager provides for the configuration of a level offset to allow
the user to calibrate the hydrostatically measured level, this is called the Level
Offset. The find level is calculated as follow.
Where L
off
= Level Offset
Where H
b
= corrected height of the bottom pressure instrument
H
m
= corrected height of the middle pressure instrument
P
b
= Bottom Pressure
P
t
= Top Pressure
P
m
= Middle Pressure
L
h
()Level H
b
P
b
P
t
P
b
P
m
-------------------
H
m
H
b
()×+=
Level L
off
L
h
+=