Tank Alarms Data
ADM003GVAE1005 359
LEAK DATA
Allows an Enable/Disable State. This alarm, when enabled, will alert every day at 12:00 AM to notify the operator
that there is not enough valid data or quiet time data from the configured tank to produce a valid Leak Test
Report
DIGITAL ALARMS - STANDARD TANK ALARM FLAGS
This variable is the current standard digital alarm statuses associated with the Tank. Available status are:
0x1-DB Config Error
0x2-Tank Calc Error
0x4-Strap Error
0x8-API Corr Error
0x10-Critical Zone
0x20-Movement Alarm
0x40-Reverse Flow
0x80-No Flow
0x100-ETA HiHi Level
0x200-ETA High Level
0x400-ETA LoLo Level
0x800-ETA Low Level
0x2000-Testing
0x4000-Trans Adv SetPt
0x8000-Trans SD SetPt
TANK MODE ALARM - COMPOSITE TANK MODE ALARM
This variable is a composite value that displays a coded variable representing the highest priority tank mode
alarms for the tank. Possible values are Normal, Movement Alarm, No Flow, Reverse Flow or Testing.
FuelsManager calculates this alarm based on the current product movement of the tank and the currently
operator selected tank mode
ALARM API CORRECTION - API CORRECTION ERROR
This variable is a coded variable value that displays a status of either Normal or API Corr Error if the Density or
Temperature is outside of the range for the selected volume correction method
ALARM CALCULATION - CALCULATION ERROR
This variable is a coded variable value that displays a status of either Normal or Tank Calc Error if
FuelsManager is unable to perform the tank volume calculation due to an internal error
ALARM CRITICAL ZONE - LEVEL IN CRITICAL ZONE
This variable is a coded variable value that displays a status of either Normal or Critical Zone if the current tank
level is between the Fully Floating and Fully Landed heights
ALARM DAtabASE CONF - DAtabASE CONFIGURATION ERROR
This variable is a coded variable value that displays a status of either Normal or DB Config Error if
FuelsManager is unable to perform operation for this tank due to an internal configuration error
ALARM ETA HIGH LEVEL - HIGH LEVEL ETA ALARM
Tank Alarms Data